Siemens UH50 Series Configuration Instructions page 8

Static heat- and cold meter
Hide thumbs Also See for UH50 Series:
Table of Contents

Advertisement

The pulse module permits the output of pulses that
can be derived from the quantity of energy, the
volume, tariff register 1 or tariff register 2. Two
channels are available whose functions can be
parameterized with the service software.
Output takes the form of standard pulses or "fast
pulses". The pulse duration is identical for channel 1
and channel 2.
Note: If two pulse modules are plugged, please note
the restrictions!
Parameter setting for standard pulses
Output mode
CE
(count energy)
C2
(count tariff 2)
CV
(count volume)
CT
(count tariff 1)
RI
(ready indication)
Parameter setting for "fast pulses"
Channel 1
CE
(count energy)
CV
(count volume)
CE / CV *)
(count energy / count volume)
*) automatic output of the higher pulse rate
Labeling
pulse module
Display in LCD
CE, C2, CV, CT or RI
Type
open collector
Voltage
maximal 30 V =
Current
maximal 30 mA
Dielectric strength
500 V
Classification
OB (per EN 1434-2)
Voltage drop
approx. 1.3 V at 20 mA
Classification
OC (per EN 1434-2)
Voltage drop
approx. 0.3 V at 0.1 mA
Output connection
(standard version):
A special version of the pulse module is available
with an Opto-MOS output.
Advantages: low voltage drop and polarized
(bipolar).
Standard pulses
Standard pulse significances
kWh *)
1 kWh
MJ *)
1 MJ
0,1 m³
0,6
2,5 3,5
Nom. flowrate in m³/h
*) depending on the unit for heat display
Ultraheat / Ultracold UH50
Output value
Pulses for quantity of energy
Pulses for tariff register 2
Pulses for volume
Pulses for tariff register 1
Pulses for the operating states
"Ready / Fault"
Channel 2
CV (count volume)
- (no function)
CV (count volume)
- (no function)
CV (count volume)
- (no function)
against ground
rms
10 kWh
10 MJ
100 MJ
1 m³
10
15 25
40
60
Configuration Instructions
Pulses for quantity of energy, volume, tariff
register
Period duration
Pulse duration
Pulses for operating states:
"Ready"
pulsed "conducting", i.e.
0.1...0.25 ms pulse duration,
500 ms period
"Fault"
constantly "non-conducting"
Fast pulses
Note: In battery operation, a D cell is required!
For applications, such actuating controllers or as
flowrate transmitters, higher pulse rates are required.
The parameters required for this (pulse significance,
pulse duration), can be configured with the service
software.
The maximum pulse frequency is 33 Hz.
The following can be set:
• Pulse type: "linear" or "scaled" pulses *)
• Pulse output: energy or volume
• Pulse duration, if only 1 pulse module is fitted:
from 2 ms to 100 ms in steps of 1 ms;
Pulse duration, if 2 pulse modules are fitted:
von 5 ms to 100 ms in steps of 5 ms
The pulses can be received and evaluated with a
suitable device. The settings must be made in
accordance with the information on the data sheet of
the controller.
*) Linear pulses are output proportionally to the
measured value. In the case of scaled pulses, the
number of pulses at the upper and lower end of the
range can be defined. In this case, the pulse
receiving device can detect, for example, a
connection error.
Linear pulses
CL module
UH 106-101k
> 200 ms
100 ms conducting
Scaled pulses (example)
Page 8 / 15

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Uh50 ultraheatUh50 ultracoldUh50 flow sensor

Table of Contents