Schematic & Termination Diagram 18 To - Trane RAUP 250 Installation Operation & Maintenance

Split system condensing units 20-55 tons
Hide thumbs Also See for RAUP 250:
Table of Contents

Advertisement

Schematic &
Termination Diagram
S TAR TER CONTR OLLER MODULE - I/O
INPU T
LPCO1
LPCO 1
39
40
COM 0
40
HPCO1
HPCO 1
41
OL 1
42
OL1
43
COM 0
43
OL2
OL 2
44
HMW T 1
45
HMWT1
46
COM 0
46
HMWT2
HMW T 2
47
-
-
LPCO2
50
LPCO 2
51
COM 0
51
HPCO2
HPCO 2
52
OL 3
53
OL3
54
COM 0
54
OL4
OL 4
55
HMW T 3
56
HMWT3
57
COM 0
57
HMWT4
HMW T 4
58
2
S1
TO TEM P. CONTR OLLER STE P 1
COM 0
TO TEM P. CONTR OLLER STE P 2
S2
2
S3
TO TEM P. CONTR OLLER STE P 3
COM 0
TO TEM P. CONTR OLLER STE P 4
S4
INPU T: USE BLA CK COLOR 0.5 SQMM.
CIRCUI T B
CIRCUI T A
C3
C2
C4
C1
CONTR OL BO X
WIRING :-RA UP600
TYPICA L WIRING FOR RA UP600
J1
RESE T 1
RESE T 2
A CIRCUI T
RESE T 3
COMPRESSORS
SYSTEM RESE
T
RESE T 1 = RESE T CIRCUI T A ON ERR OR
RESE T 2 = RESE T CIRCUI T B ON ERR OR
SYSTEM RESE
T : = RESE T SYSTEM ON ERR
OR
COM P. : S TAR T-UP TIMING
B CIRCUI T
A CIRCUI T A-C1 ON DEL AY TIME = 1 min
COMPRESSORS
A CIRCUI T A-C2 ON DEL AY TIME = 2 min
B CIRCUI T B-C3 ON DEL AY TIME = 1.5 min
B CIRCUI T B-C4 ON DEL AY TIME = 2.5 min
FAN FOR
RA UP MODE L ON LY
WARNING :
- CON TAC T INPUTS ON LY
- NO AC SIGNA L AT INPUTS
7 SEGMEN T DISPL AY CODE TABLE
7 Segment Displa y
Error Descr iption
--
NORMA L
L1
LPCO 1 Error
H1
HPCO 1 Error
O1
OL 1 Error
O2
OL 2 Error
t1
HMW T 1 Error
t2
HMW T 2 Error
L2
LPCO 2 Error
H2
HPCO 2 Error
O3
OL 3 Error
O4
OL 4 Error
t3
HMW T 3 Error
t4
HMW T 4 Error
S1 - S4
THERMOS TAT S TATUS
NO TES:
NO TES:
1
TERMIN ATION (CONTR OL)
N
2
32
33
30
3
4
TB T1
T2
T3
3
29
RAUP 600
OUTPU T
J3
COM 1
33
A-C1
34
COM 2
33
A-C2
35
COM 3
33
B-C3
36
COM 4
33
B-C4
37
COM 5
33
C5
38
T2
ALM/NC
COM
ALM/NO
TRI P
LIGH T
L (240 V)
N
CIRCUI T A
CIRCUI T B
J5
OUTPU T: USE BLA CK 1 SQMM.
DASHED LINES INDIC
ATE RECOMMENDED FIELD
WIRING B Y O THERS . DASHED LINE ENCLOSURES
AND/OR D ASHED DEVICE OUTLINES INDIC
ATE
COMPONENTS PR
OVIDED B Y THE FIELD . PHAN TOM
LINE ENCLOSURES INDIC
ATE ALTERN ATE
CIRCUIT R Y OR AVAILABLE SALES OPTIONS
.
SOLID LINE INDIC
ATES FAC TOR Y WIRING.
REMO VE JUMPER
WHEN TEMPER ATURE CONTR
IS INS TALLED
REMO VE JUMPER
T O INTER FACE WITH EVF
INTERLOCK
PRESS SW3 B
UT TON FOR SHO W THE MEMORABLE ERR
THE 7-SEG
WIL L OFF FOR 2 SECONDS BEFORE DISPL
MOMORABLE ERR
OR CODES
TH AT ARE THE CA USES OF
EA CH LOCK OU T. AFTER TH AT THE 7-SEG
WIL L OFF FOR
2 SECONDS
AND RETURN
T O DISPL AY THE EXISTING
ERR OR/S TATUS CODES .IF MORE
THAN 1 ERR OR HAPPENS
THE Y ARE DISPL AYED 2 SECOND EA
CH.IF THERE IS NO
MEMORABLE ERR
ORS ,THE NORMA L CODE WIL L BE DISPL AYED .
PRESS
AND HOLD SW3 B
UT TON FOR 4 SECONDS
CLEAR THE MEMORABLE ERR
OR.
WARNING
HAZARDOUS
VO LTAGE!
DISCONNEC
T AL L ELECTRIC PO
WER
INCLUDING REMO
TE DISCONNECTS
BEFORE SE
R VICING.
FAILURE T O DISCONNEC
T PO WER
BEFORE SE
R VICING CAN CA
USE
SEVERE PERSONA
L INJU R Y OR DE ATH.
IMPO R TAN T
USE COPPER CONDUC
T ORS ON LY
T O PREVEN
T EQ UIPMEN T DAMA GE.
UNI T TERMINALS
ARE NO T DESIGNED
T O ACCEP T AN Y O THER WIRING.
A-C1
A-C2
B-C3
B-C4
C5
T3
OLLER
OR.
AY THE
,
T AN Y
T O
035-0766G

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Raup 300Raup 400Raup 500Raup 600

Table of Contents