Trane RAUP 250 Installation Operation & Maintenance page 23

Split system condensing units 20-55 tons
Hide thumbs Also See for RAUP 250:
Table of Contents

Advertisement

Schematic &
Termination Diagram
STARTER CONTROLLER MODULE - I/O WIRING :-RAUP250
LPCO1
LPCO 1
38
39
COM 0
39
HPCO1
HPCO 1
40
COM 0
JUMPER
HMWT 1
COM 0
JUMPER
HMWT 2
LPCO 2
COM 0
JUMPER
HPCO 2
COM 0
JUMPER
HMWT 3
COM 0
JUMPER
HMWT 4
2
TO TEMP. CONTROLLER STEP 1
COM 0
JUMPER
2
TO TEMP. CONTROLLER STEP 2
COM 0
JUMPER
INPUT: USE BLACK COLOR 0.5 SQMM.
C1
C2
WARNING
HAZARDOUS VOLTAGE!
DISCONNECT ALL ELECTRIC POWER
INCLUDING REMOTE DISCONNECTS
BEFORE SERVICING.
FAILURE TO DISCONNECT POWER
BEFORE SERVICING CAN CAUSE
SEVERE PERSONAL INJURY OR DEATH.
IMPORTANT
USE COPPER CONDUCTORS ONLY
TO PREVENT EQUIPMENT DAMAGE.
UNIT TERMINALS ARE NOT DESIGNED
TO ACCEPT ANY OTHER WIRING.
INPUT
TYPICAL WIRING FOR RAUP 250
J1
RESET 1
RESET 2
RESET 3
SYSTEM RESET
OL 1
RESET 1 = RESET CIRCUIT A ON ERROR
RESET 2 = RESET CIRCUIT B ON ERROR
OL 2
SYSTEM RESET : = RESET SYSTEM ON ERROR
COMP. : START-UP TIMING
A CIRCUIT A-C1 ON DELAY TIME = 1 min
A CIRCUIT A-C2 ON DELAY TIME = 2 min
-
RAUP MODEL ONLY
-
WARNING :
- CONTACT INPUTS ONLY
- NO AC SIGNAL AT INPUTS
OL 3
OL 4
7 SEGMENT DISPLAY CODE TABLE
7 Segment Display
Error Description
--
NORMAL
L1
LPCO 1 Error
S1
H1
HPCO 1 Error
O1
OL 1 Error
O2
OL 2 Error
S2
t1
HMWT 1 Error
t2
HMWT 2 Error
S3
L2
LPCO 2 Error
H2
HPCO 2 Error
O3
OL 3 Error
S4
O4
OL 4 Error
t3
HMWT 3 Error
t4
HMWT 4 Error
S1 - S4
THERMOSTAT STATUS
TERMINATION (CONTROL)
N
32
33
30
T1 T2
T3
3
20
OUTPUT
J3
COM 1
A-C1
A CIRCUIT
COMPRESSORS
COM 2
A-C2
COM 3
B-C3
COM 4
B-C4
COM 5
FAN FOR
C5
J4
ALM/NC
COM
ALM/NO
CIRCUIT A
CIRCUIT B
J5
OUTPUT: USE BLACK 1 SQMM.
NOTES:
1
DASHED LINES INDICATE RECOMMENDED FIELD
WIRING BY OTHERS. DASHED LINE ENCLOSURES
AND/OR DASHED DEVICE OUTLINES INDICATE
COMPONENTS PROVIDED BY THE FIELD. PHAN TOM
LINE ENCLOSURES INDICATE ALTERNATE
CIRCUITRY OR AVAILABLE SALES OPTIONS.
SOLID LINE INDICATES FACTORY WIRING.
2
REMOVE JUMPER WHEN TEMPERATURE CONTROLLER
IS INSTALLED
TB
3
REMOVE JUMPER TO INTERFACE WITH EVF
INTERLOCK
4
PRESS SW3 BUTTON FOR SHOW THE MEMORABLE ERROR.
THE 7-SEG WILL OFF FOR 2 SECONDS BEFORE DISPLAY THE
MOMORABLE ERROR CODES THAT ARE THE CAUSES OF
EACH LOCKOUT. AFTER THAT THE 7-SEG WILL OFF FOR
2 SECONDS AND RETURN TO DISPLAY THE EXISTING
ERROR/STATUS CODES.IF MORE THAN 1 ERROR HAPPENS,
THEY ARE DISPLAYED 2 SECOND EACH.IF THERE IS NOT ANY
MEMORABLE ERRORS,THE NORMAL CODE WILL BE DISPLAYED.
PRESS AND HOLD SW3 BUTTON FOR 4 SECONDS TO
CLEAR THE MEMORABLE ERROR.
RAUP 250
33
A-C1
34
33
A-C2
35
33
C5
36
T3
T2
TRIP
LIGHT
N
L (240 V)

Hide quick links: