TABLE 16: ELECTRICAL DATA - BB-05 BELT DRIVE WITH POWR'D CONVENIENCE OUTLET
Model
Voltage
Tonnage
Each
208-1-60
230-1-60
208-3-60
5
230-3-60
460-3-60
575-3-60
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.
TABLE 17: ELECTRIC HEAT CORRECTION
FACTORS
NOMINAL VOLTAGE
VOLTAGE
208
240
480
600
Unitary Products Group
Compressors
OD Fan
ID Blower
Motor
Motor
RLA
LRA
FLA
FLA
Each
32.1
148
2.3
32.1
148
2.3
19.3
137
2.3
19.3
137
2.3
10.0
62
1.3
7.9
50
1.3
kW CAP. MULTIPLIER
208
1.00
230
0.92
460
0.92
575
0.92
Conv
Electric Heater
Outlet
Model No.
Amps
NONE
2CE04510506
2CE04510706
7.6
10.0
2CE04511006
2CE04511506
2CE04512006
2CE04513006
NONE
2CE04510506
2CE04510706
7.6
10.0
2CE04511006
2CE04511506
2CE04512006
2CE04513006
NONE
2CE04510525
2CE04510725
5.2
10.0
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE04510525
2CE04510725
5.2
10.0
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE04510746
2CE04511046
2.6
5.0
2CE04511546
2CE04512046
2CE04513046
NONE
2CE04511058
2
4.0
2CE04511558
2CE04512058
2CE04513058
TABLE 18: VOLTAGE LIMITATIONS
POWER SUPPLY
208/230-3-60
460-3-60
575-3-60
1.
Utilization Range "A" in accordance with ARI Standard
110.
Minimum
Heater
Heater
Circuit
kW
Amps
Ampacity
Amps
0.0
0.0
60.0
4.0
19.2
84.1
5.6
26.9
93.7
8.0
38.5
108.1
11.9
57.2
131.5
15.9
76.4
155.6
22.2
106.7
193.4
0.0
0.0
60.0
5.3
22.1
87.6
7.5
31.3
99.1
10.6
44.2
115.2
15.9
66.3
142.8
21.2
88.3
170.4
29.6
123.3
214.2
0.0
0.0
41.6
2
4.0
11.1
55.5
2
5.6
15.5
61.1
8.0
22.2
69.4
11.9
33.0
82.9
15.9
44.1
96.8
22.2
61.6
118.7
0.0
0.0
41.6
2
5.3
12.7
57.6
2
7.5
18.0
64.2
10.6
25.5
73.5
15.9
38.2
89.4
21.2
51.0
105.4
29.6
71.2
130.6
0.0
0.0
21.4
2
6.8
8.2
31.6
2
10.1
12.1
36.6
2
13.6
16.4
41.8
2
19.5
23.5
50.7
2
28.8
34.6
64.7
0.0
0.0
16.5
10.6
10.2
29.3
15.9
15.3
35.6
21.2
20.4
42.0
30.4
29.3
53.1
VOLTAGE
MIN.
187
414
518
Max Fuse /
1
BRKR
Size
Amps
90
110
110
125
150
175
200
90
110
110
125
150
175
225
60
70
70
80
90
100
125
60
70
70
80
90
110
150
30
35
40
45
60
70
20
30
40
45
60
1
MAX.
253
506
630
27