4.2
TABLE 2: Configuration DIP Switch Settings
Verification Time
DIP SWITCH
DIP SWITCH
1
closed
closed
open
closed
open
closed
open
open
Latching
DIP SWITCH
4
open
closed
IR-Only Enable
DIP SWITCH
5
open
closed
Test Cycle
DIP SWITCH
6
open
closed
Fire Range
DIP SWITCH
7
open
closed
open
closed
HONEYWELL
Detector Switch Options
DIP SWITCH
2
3
closed
closed
open
open
closed
open
closed
open
open
closed
open
closed
closed
closed
open
open
DESCRIPTION
Non-Latching mode. If Verify is enabled then the Verify Relay will de-energize
approximately 10 seconds after it energizes. If Verify is disabled then the Fire
Relay(s) will de-energize approximately 10 seconds after it energizes. The SS4-A2
Factory setting is Non-Latching
Latching mode. If Verify is enabled then when the Verify Relay energizes it will
remain energized until the Detector is reset. If Verify is disabled then when the Fire
Relay energizes it will remain energized until the Detector is reset. The SS4-A
Factory setting is latching
DESCRIPTION
Fire Alarm declaration UV and IR energy. Factory setting
A Fire Alarm may be declared without UV being detected.
DESCRIPTION
Testing of the Lens occurs every 30 minutes. Factory setting
*Testing of the Lens occurs every 6 minutes
* Utilization of the 6-minute period may adversely affect the source tube service life.
DIP SWITCH
DESCRIPTION
8
open
Set to detect an industry standard 1 sq. ft. fire at 15 ft. on axis.
open
Set to detect an industry standard 1 sq. ft. fire at 30 ft. on axis.
closed
Set to detect an industry standard 1 sq. ft. fire at 45 ft. on axis.
Factory setting
closed
Set to detect an industry standard 1 sq. ft. fire at 60 ft. on axis.
OPERATOR MANUAL // SECTION 4
DETECTOR CONNECTIONS & SWITCH OPTIONS
DESCRIPTION
Verify is disabled and the Verify Relay is unused.
Factory setting
Verify is enabled and the Verify time is 5 seconds.
Verify is enabled and the Verify time is 10 seconds.
Verify is enabled and the Verify time is 15 seconds.
Verify is enabled and the Verify time is 20 seconds.
Verify is enabled and the Verify time is 25 seconds.
Verify is enabled and the Verify time is 30 seconds.
Verify is disabled and the Verify Relay operates as a
second Fire Relay.
26