Model SS4-AUV/-AUV2 Ultraviolet (UV) Digital Electro-Optical Fire Detector
Installation Guide and Operating Manual
MAN0927_V3_1510-005_Rev H_06-13

Verification Time

DIP SWITCH
DIP SWITCH
1
closed
closed
closed
open
closed
closed
closed
open
closed
open
closed
open

Latching

DIP SWITCH
4
open
Non-Latching mode. If Verify is enabled then the Verify Relay will de-energize approximately 10
seconds after it energizes. If Verify is disabled then the Fire Relay(s) will de-energize
approximately 10 seconds after it energizes. The SS4-AUV2 Factory setting is Non-Latching
closed
Latching mode. If Verify is enabled then when the Verify Relay energizes it will remain
energized until the Detector is reset. If Verify is disabled then when the Fire Relay energizes it
will remain energized until the Detector is reset. The SS4-AUV Factory setting is Latching
DIP SWITCH
5
N/A
DIP SWITCH 5 is not used in the SS4-AUV/-AUV2

Test Cycle

DIP SWITCH
6
open
Testing of the Lens occurs every 30 minutes. Factory setting
closed
* Testing of the Lens occurs every 6 minutes
* Utilization of the 6-minute period may adversely affect the source tube service life.

Fire Range

DIP SWITCH
DIP SWITCH
7
open
closed
open
closed
TABLE 2: Configuration DIP Switch Settings
DIP SWITCH
2
3
closed
Verify is disabled and the Verify Relay is unused. Factory setting
open
open
Verify is enabled and the Verify time is 5 seconds.
open
Verify is enabled and the Verify time is 10 seconds.
open
Verify is enabled and the Verify time is 15 seconds.
open
closed
Verify is enabled and the Verify time is 20 seconds.
open
closed
Verify is enabled and the Verify time is 25 seconds.
closed
Verify is enabled and the Verify time is 30 seconds.
open
open
Verify is disabled and the Verify Relay operates as a second Fire Relay.
DESCRIPTION
DESCRIPTION
DESCRIPTION
DESCRIPTION
8
open
Set to detect an industry standard 1 sq. ft. fire at 15 ft. on axis.
open
Set to detect an industry standard 1 sq. ft. fire at 30 ft. on axis.
closed
Set to detect an industry standard 1 sq. ft. fire at 45 ft. on axis. Factory setting
closed
Set to detect an industry standard 1 sq. ft. fire at 60 ft. on axis.