Detector Connections & Switch Options - Honeywell SS4-AS Installation Manual And Operating Manual

Multi-spectrum digital electro-optical fire detector
Table of Contents

Advertisement

SECTION 4
DETECTOR CONNECTIONS & SWITCH OPTIONS
4.1
HONEYWELL
Detector Connections
TABLE 1: Stand-Alone Model SS4-A/-A2 Detector
Connectors - Pinouts
J1:
DETECTOR INPUT POWER
PIN
1
DC Return ( - )
2
RS-485 Connection to an optional interface unit for
viewing FirePic and TriMode Plot.
3
RS-485 Connection to an optional interface unit for viewing
FirePic and TriMode Plot.
4
Power (+24 Volts DC)
J2:
DETECTOR POWER OUT
PIN
1
DC Return ( - )
2
RS-485 Connection to an optional interface unit for viewing
FirePic and TriMode Plot.
3
RS-485 Connection to an optional interface unit for viewing
FirePic and TriMode Plot.
4
Power (+24 Volts DC)
J4:
FIRE RELAY
PIN
1
Fire Relay Common
2
Fire Relay Normally Closed
3
Fire Relay Common
4
Fire Relay Normally Open
J5:
FAULT RELAY (Energized)
PIN
1
Fault Relay Normally Open
2
Fault Relay Common
3
Fault Relay Normally Closed
4
Fault Relay Common
OPERATOR MANUAL // SECTION 4
DETECTOR CONNECTIONS & SWITCH OPTIONS
J6:
FIRE VERIFY RELAY
PIN
1
Verify Relay Common
2
Verify Relay Normally Open
3
Verify Relay Common
4
Verify Relay Normally Closed