Summary of Contents for Schaffner Ecosine max FN 3470
Page 1
FN 3480/FN 3481 (50 Hz) for 440–480 VAC FN 3472/FN 3473 (60 Hz) for 380–415 VAC English version (original instructions) FN 3482/FN 3483 (60 Hz) for 440–480 VAC Schaffner Group Nordstrasse 11e 4542 Luterbach Switzerland T +41 32 681 66 26 info@schaffner.com...
Page 2
Manual at any time without obligation to notify any person of such revision or changes. Schaffner will make all possible efforts to secure the accuracy and the integrity of this Manual. Schaffner disclaims any kinds or forms of warranty, guarantee, or undertak- ing, either expressly or implicitly, including but not limited to the completeness, faultlessness, accuracy, non-infringement, merchantability or fitness for a particular purpose of the Manual.
Page 3
The most current edition of this document (PDF format) and official translations can be obtained from your contact of the Schaffner organization or online at schaffner.com Other technical documentation of our products is also available in the download area of our website schaffner.com/downloads...
This user manual is intended to support designers, installers, and application engineers with filter se- lection, installation, application, and maintenance. It provides helpful solutions to overcome harmonics mitigation challenges and answers frequently asked questions. If you require additional support, please feel free to contact Schaffner or our local partner. 3/66 schaffner.com...
Line voltage unbalance: <1% Line voltage distortion: THDv <2% If a properly sized and installed filter fails to meet the 5% THDi level, Schaffner will provide the neces- sary application engineering support or filter replacement at no charge. Important user notice...
Schaffner Group User and Installation Manual Ecosine max General Safety Notes and Installation Guidelines (Cautions and Warnings) 5/66 schaffner.com...
Schaffner Group User and Installation Manual Ecosine max Content Ecosine max passive harmonic filter ................... 3 Performance Guarantee ......................... 4 iii. Minimum system Requirements....................4 Important user notice ......................... 4 General Safety Notes and Installation Guidelines (Cautions and Warnings) ......5 Ecosine max passive harmonic filter designation ..........
Page 8
Schaffner Group User and Installation Manual Ecosine max Cabinet specifications ......................30 3.10 Cooling requirement ......................32 3.10.1 Additional requirement for cooling ..................33 3.11 Mechanical frame sizes ......................36 3.12 Ecosine max passive harmonic filter footprint ..............37 3.13 Filter performance .........................
Page 9
Schaffner Group User and Installation Manual Ecosine max 8.3.6 Connect monitor switch TS- TS’ ..................57 8.3.7 Connect auxiliary switch AS- AS’ ..................58 8.3.8 Install and connect the switch remote operator ..............59 8.3.9 Fuses ........................... 60 Filter maintenance ..................... 62 Maintenance schedule ......................
Schaffner Group User and Installation Manual Ecosine max 1 Ecosine max passive harmonic filter designation 1.1 Distinguishing between FN 3470/FN 3471, FN 3480/FN 3481, FN 3472/FN 3473 and FN 3482/FN 3483 The main difference between FN3470 (FN3472, FN3480 FN3482) and FN3471 (FN3473, FN3481, FN3483) is the filter configuration, which is clearly shown in Figure 1 and Figure 2 below.
Ecosine max 1.2 Explanation of ecosine max designation Ecosine max is part of the new generation of Schaffner passive harmonic filter. Starting from Schaffner ecosine evo series, a designation system, which contains of 4 sections connected with ‘-’ was intro- duced.
Page 12
Schaffner Group User and Installation Manual Ecosine max Examples of ecosine max filter designations: FN 3470-315-99-E0XXSXX: Filter for 50 Hz, 380–415 V AC grid, motor drive power rating 315kW, open frame (IP 00), filter contains trap disconnect switch module. Filter is expected to achieve 5% THDi for drives without DC-link choke, or 3.5% THDi for drives with 4% DC-link choke.
2 Filter selection Ecosine max passive harmonic filters need to be carefully selected and configured in order to enjoy maximum benefits. Schaffner advices to verify the selection by using the Schaffner Power Quality Sim- ulator tool SchaffnerPQS3, available at pqs.schaffner.com.
Page 14
Schaffner Group User and Installation Manual Ecosine max Please refer to the following examples: Example 1: Power line rating: 400 V, 50 Hz Drive rating: 380–500 V, 50–60 Hz, 355 kW, 727 A, B6-diode rectifier without DC-link choke Required THDi @ rated power: 5%...
Schaffner Group User and Installation Manual Ecosine max 3 Filter description 3.1 General electrical specifications FN 3470/FN 3471 (50 Hz filters) Nominal operating voltage: 3x 380 to 415 V AC Voltage tolerance range: 3x 342 to 457 V AC Operating frequency: 50 Hz ±1 Hz...
Schaffner Group User and Installation Manual Ecosine max 3.2 General electrical specifications FN 3480/FN 3481 (50 Hz filters) Nominal operating voltage: 3x 440 to 480 V AC Voltage tolerance range: 3x 396 to 528 V AC Operating frequency: 50 Hz ±1 Hz...
Schaffner Group User and Installation Manual Ecosine max 3.3 General electrical specifications FN 3472/FN 3473 (60 Hz filters) Nominal operating voltage: 3x 380 to 415 V AC Voltage tolerance range: 3x 342 to 456 V AC Operating frequency: 60 Hz ±1 Hz...
Schaffner Group User and Installation Manual Ecosine max 3.4 General electrical specifications FN 3482/FN 3483 (60 Hz filters) Nominal operating voltage: 3x 440 to 480 V AC Voltage tolerance range: 3x 396 to 528 V AC Operating frequency: 60 Hz ±1 Hz...
Schaffner Group User and Installation Manual Ecosine max 3.5 Additional electrical specifications Ecosine max passive harmonic filters general electrical specifications refer to operating altitudes up to 2000m (6600ft) above sea level. Operation between 2000m and 4000m (6600ft and 13123ft) requires a derating for current and clear-...
Page 28
Schaffner Group User and Installation Manual Ecosine max Table 20 Cable cross-section recommendation Filter Power Line Volt- Freq. Termi- Termi- Frame Min. recommended cable Rating Cur- age [V] [Hz] Size cross-section per phase rent Line Load Busbar Busbar FN3470-250-99 250 kW...
Page 29
Schaffner Group User and Installation Manual Ecosine max Figure 4 Drawing of different terminal dimensions (according to Table 20) schaffner.com 28/66...
Schaffner Group User and Installation Manual Ecosine max 3.6.2 Trap disconnect jumper terminals Cable cross section recommended for connection to the trap disconnect jumper terminals (only for configuration with this option): Table 21 recommended and maximum cable cross section for the trap disconnect jumper terminals...
(see section 3.10) might require additional validation from the customer. Schaffner is not reliable for any de- viations in the filter specifications resulting from an improper cabinet integration.
Page 32
Schaffner Group User and Installation Manual Ecosine max Table 24 Part numbers of the reference cabinets from Rittal VX25 Cabinet 800mm Cabinet 1000mm Cabinet 1200mm Baying enclosure system 8806.000 8006.000 8206.000 VX25 Basic enclosure Support Rail 48x26mm 8617.810 8617.820 8617.830 Roof-mounted fan 3140.500...
Schaffner Group User and Installation Manual Ecosine max 3.10 Cooling requirement It must be ensured that the environmental temperature is kept below 40°C with appropriate thermal management (e.g. cabinet cooling). Filter operation in environments with higher temperatures require a temperature derating.
Schaffner Group User and Installation Manual Ecosine max Figure 5 Reference cabinet with recommended air inlet placement Table 26 Dimensions for the recommended air inlet placement Dimension Cabinet 800mm Cabinet 1000mm Cabinet 1200mm 3.10.1 Additional requirement for cooling • To allow significant air flow, the fine dust filter foam need to be removed from the air inlet.
Page 35
Schaffner Group User and Installation Manual Ecosine max Figure 6 opening at the bottom and back of the cabinet (front view) Figure 7 opening at the bottom of the cabinet (top view from inside). About 1/3 remain open. schaffner.com 34/66...
Page 36
Schaffner Group User and Installation Manual Ecosine max Figure 8 opening at the back of the cabinet. Base plinth should stay open for cables entry and cooling. 35/66 schaffner.com...
Schaffner Group User and Installation Manual Ecosine max 3.11 Mechanical frame sizes All ecosine max passive harmonic filters are realized with 6 frame sizes, S08/S10/S12 and L08/L10/L12. Dimensions and footprint are provided in section 3.12. Ecosine max passive harmonic filters are IP00 and external air cooling is needed, details are provided in section 3.8.
Schaffner Group User and Installation Manual Ecosine max 3.12 Ecosine max passive harmonic filter footprint Figure 10 Mechanical data of FN 3471/73/81/83 Figure 11 Mechanical data of FN 3470/72/80/82 Table 27 Dimensions of all frame sizes in mm Frame LINE...
Page 39
Schaffner Group User and Installation Manual Ecosine max Table 28 Dimensions of all frame sizes in inches Frame LINE LOAD Recommended size cabinet size WxDxH max.25.6 max. 44.09 14.96 12.99 9.06 19.29 0.53 10.04 + 18.5 + 31.5x23.6x78.7 19.88 0.039 1.18...
Schaffner Group User and Installation Manual Ecosine max 3.13 Filter performance Ecosine max passive harmonic filters achieve 5% THDi with 6-pulse diode rectifiers under the follow- ing condition. Filter is applied to rated voltage and power THDv <2%, line voltage unbalance <1% 5% THDi is not guaranteed for thyristor rectifier application.
Page 41
Schaffner Group User and Installation Manual Ecosine max 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 Load [%] Figure 13 Power factor vs. load (diode rectifier front-ends) 90 100 110 120 130 140 150 160 170 180 Load [%] Figure 14 Drive dc-link voltage vs.
Schaffner Group User and Installation Manual Ecosine max 3.14 Functional diagram 3.14.1 Filter configuration Filter terminals Line L1/L2/L3 3 busbar terminals at line side Load L1’/L2’/L3’ 3 busbar terminals at load side TS, TS’ Connecting terminals to thermal switch NC 180°C (UL- approved) to detect overload in chokes AS, AS’...
Schaffner Group User and Installation Manual Ecosine max 3.14.2 Filter configuration -E0XXJXX Filter terminals Line L1/L2/L3 3 busbar terminals at line side Load L1’/L2’/L3’ 3 busbar terminals at load side TS, TS’ Connecting terminals to thermal switch NC 180°C (UL- approved) to detect overload in chokes AS, AS’...
Schaffner Group User and Installation Manual Ecosine max 4 Ecosine max harmonic filter schematics and working principle The base module of FN 3471, FN3473, FN 3481 and FN 3483 series contains line choke, trap choke and trap capacitor, which helps reduce THDi to 5% for motor drives with an 4% DC-link choke present.
Schaffner Group User and Installation Manual Ecosine max 5 Filter appearance and elements Ecosine max passive harmonic filters are available in IP00 open frame, and all designed for floor- mounted installation. The compact design makes it an optimized open frame for cabinet integration.
Schaffner Group User and Installation Manual Ecosine max Figure 18 Design of FN3470/80/72/82 filter (Type E0XXSXX) 5.2 Mechanical design of FN3471/81/73/83 (without load choke present) The general design of FN3471/81/73/83, filters without load choke present, and with circuit breaker module (E0XXSXX) is shown in Figure 19.
Page 47
Schaffner Group User and Installation Manual Ecosine max Figure 19 Design of FN3471/81/73/83 filter (Type E0XXSXX) schaffner.com 46/66...
Ecosine max 6 Performance estimation using SchaffnerPQS Ecosine max passive harmonic filters are included and can thus be simulated with the Schaffner Power Quality Simulator SchaffnerPQS (pqs.schaffner.com). By using SchaffnerPQS, users can easily simulate and estimate system performance taking into ac- count the most important design requirements and system’s boundary conditions.
Schaffner Group User and Installation Manual Ecosine max 7 Filter application Ecosine max passive harmonic filters are designed to mitigate harmonic current of non-linear loads, particularly of three-phase diode-type rectifiers. Contrary to “bus-applied or PCC (Point of Common Coupling)” filters, which are being installed e.g. at the main feeder, ecosine passive harmonic filters are specifically designed to be used with either an individual non-linear load, or with a group of non- linear loads.
Page 50
Schaffner Group User and Installation Manual Ecosine max Figure 21 Application example with 2 filters in parallel for larger load 49/66 schaffner.com...
In the case of damage, please file a claim with the freight forwarder involved immediately and contact Schaffner or our local partner for support. Under no circumstances install and energize a filter with suspected transportation damage, whenever it is clearly visible or not.
Schaffner Group User and Installation Manual Ecosine max If the filter is not going to be put in service upon receipt, store within the original container in a clean, dry location, free of dust and chemicals and with respect to named temperature limits, see section 2.
Schaffner Group User and Installation Manual Ecosine max 8.2.1 Fixation Screw hole positions for mounting the filters as indicated in Table Table 29 Dimensions of frame sizes Figure 24 Fixation points for fil- Frame size Drill pattern [mm] ters FN 3470, FN 3472, FN 3480 and FN 3482 T = 13.5 mm for all frame sizes...
For the other part of the bolts (respectively the nut or screw) Schaffner recommends zinc coated hex ribbed flange steel screws or nuts. Respect filters weight for appropriate choice of screws! Head diameters must not exceed these dimensions: M12: d ≤24 mm...
Page 55
Schaffner Group User and Installation Manual Ecosine max Danger: respect lifting angle, risk of severe dam- The maximum allowed angle between the lifting rope and verti- cal plan should not exceed 45°. Failing to comply might destroy the equipment and induce a risk of severe injuries.
Schaffner Group User and Installation Manual Ecosine max 8.3 Step 3: Wiring 8.3.1 Verify safe disconnection of all line side power Consult your local safety instructions. 8.3.2 Carefully connect protective earth (PE) cable to adequate earth potential close to ecosine filter Use a cable with diameter of equal or bigger size as fore- seen for line/load side power cables –...
Schaffner Group User and Installation Manual Ecosine max 8.3.4 Connect ecosine main terminals to the re- spective phase on the line and load/rectifier The main cables must have an appropriate M12 ca- ble lug. In case of busbar connections, the contact...
E0XXJXX figuration allows to install any third party switch circuit The nominal power rating in kW breaker (not supplied by Schaffner) and when necessary an multiples 20% and the grid voltage, additional capacitor contactor (not supplied by Schaffner). then divided by the nominal voltage...
Schaffner Group User and Installation Manual Ecosine max 8.3.7 Connect auxiliary switch AS- AS’ For filter configuration with S option (pre-equipped with switch, see sections 2.1 to 2.4) Warning: an engaged auxil- iary switch not resulting from a The auxiliary switch is a contact, which indicates state of cir- manual or remote controlled open- cuit breaker.
The remote operator for the switch allows to control remotely the switch on order when required for the application. The remote operator module is not provided by Schaffner and when required, it need to be bought separately. Please consult the relevant user manual for complete installation and usage.
Schaffner Group User and Installation Manual Ecosine max 8.3.9 Fuses Ecosine max passive harmonic filters need external over-current protection for compliance with UL/cUL standard. Fuses and associated fuse holders must be UL listed and rated for 100kA SCCR supplies. Table 30 and Table 31 show requested fuse current ratings for UL class J/L and, where UL compliance is not mandatory, for IEC class gG.
Page 62
Schaffner Group User and Installation Manual Ecosine max Table 30 Requested fuse current rating for UL class J/L and for IEC class gG Ecosine ecosine ecosine ecosine Fuse class Fuse class All FN 3470 All FN 3471 All FN 3480...
Schaffner Group User and Installation Manual Ecosine max 9 Filter maintenance Ecosine max passive harmonic filters described in this manual are equipped with long life components that ensure a satisfactory function for many years under normal operating conditions. Any operation under extreme conditions such as over-temperatures, overvoltage situations, polluted environments etc.
Therefore, Schaffner recommends checking and tighten all electrical connections when a regular scheduled maintenance of the entire device that incorporates the filter is ongoing. Check of internal connections within the filters is not needed or should be conducted by a Schaffner service representative.
Schaffner Group User and Installation Manual Ecosine max 10 Trap circuit disconnect The trap disconnect jumper is an option allowing to connect a third party switch and, when required, to add a capacitor contactor in series for the purpose of reducing the capacitive current during low load operation.