until the adsorbents reach saturation. At saturation, the
adsorbents emit a continuous strong pungent odor. If the
air cleaner is turned off for 8 to 10 hours, there will a
temporary odor when it is turned back on. If the odor
persists for 30 minutes, it is time to replace the filters.
Prefilter, Media Filters and CPZ
Modules
The disposable prefilter collects large dust particulates
and lint- type airborne fibers. Check the filter every 3
months to determine the replacement frequency:
IMPORTANT
Do not touch the pleated filter media. Handle only
the filter frame to prevent damage to the filter
media.
1. Verify power shut off
2. Remove the air cleaner cover and set aside.
3. Remove the prefilter and primary filters.
4. Check the prefilter and replace if it is fully coated
with dust and lint. (approximately every 3 months)
5. Replace the primary media filter(s) when there is a
noticeable loss of air volume from the air cleaner
(approximately every 12 - 18 months)
Model*
Motor will not start
Vibration - High
Frequency
Vibration - Low
Frequency
Scraping noise
Squeal or whistle noise
F116 SERIES 2 SELF-CONTAINED DUCTABLE COMMERCIAL AIR CLEANER
Table 4. Troubleshooting the F116 Series 2 Air Cleaner
• Check wiring for loose connections - Tighten if necessary.
• Check capacitor - Replace if necessary.
• Check for hot motor - Thermal protection relay is tripped,
reset it.
• Replace motor.
• Check that blower wheel is balanced - remove and balance or
replace wheel.
• Check if system is operating above 2.0" W.G. pressure - reduce
total pressure by replacing filters.
• Check if the blower wheel is touching the blower housing -
adjust blower and position wheel in the center of the inlet
ring.
• Check for air leaks in the cabinet doors or ducting - plug air
leaks.
6. Replace the CPZ sorbent modules when a continu-
ous noticeable odor is emitted from the air cleaner.
(approximately every 4 to 12 months).
7. Reassemble the air cleaner and turn the power on.
On initial startup, a small amount of dust can blow from
the air cleaner. This is normal and stops a few minutes
after startup. After running the unit for 5 minutes, turn off
the unit, the unit is ready for operation.

TROUBLESHOOTING

CAUTION
Electrical Hazard.
Can cause personal injury or equipment damage.
The following procedures expose hazardous live
parts. Disconnect power before installing or
servicing the air cleaner.