INSTALLATION INSTRUCTIONS

Installation: Mechanical Connection
1. Ceiling
3/4'' NPT
Step 1
Step 1:
Mark and drill desired location on mounting surface. Secure the driver housing cover with (4) M10 expansion bolts
(not provided) directly to a structural member. Thread onto a 3/4" NPT conduit.
Step 2:
Hang the fixture onto the hinged hook of the driver housing cover. Connect supply wires to luminaire wire leads (or
Wago connectors provided).
Step 3:
Close driver housing, making sure that all wires are safely tucked inside housing. Tighten (3) M6 captive closing
screws to 6 N-m. Ensure NPT fittings are water tight to prevent water leakage.
2. Bracket
Expansion bolts
(Gasket + Washers required ) M10
Soket head cap screw M5
Soket head cap screw M10
Step 1
Figure 1a
Step 1:
Secure the bracket and driver housing cover with (4) M10 expansion bolts (not provided) directly to a structural member, make
sure the hinge is located as marked (See Figure 1a). Adjust the angle of the bracket (6x15°) and fix the position with M5
screws (provided).
Step 2:
Hang the fixture onto the hinged hook of the driver housing cover. Connect supply wires to luminaire wire leads (or
Wago connectors provided).
Step 3:
Close driver housing, making sure that all wires are safely tucked inside housing. Tighten (3) M6 captive closing
screws to 6 N-m. Ensure NPT fittings are water tight to prevent water leakage.
LDPI, Inc. | (800)-854-0021 | www.ldpi-inc.com | sales@ldpi-inc.com
Expansion bolts
(Washers required ) M10
3/4'' NPT
Step 2
Step 2
LEHL2
Step 3
Angle 0-90° Adjustable
Step 3
v.06.18.20
Page 4