Setting the function
Select the mode/function/option/value using '▶', '◀' Button and con-
firm that using the '●' button after dip switch No.5 is turned on.
DIP-SW01 7 - Segment
Mode
Function
Option
Content Display1
Content
Display2
Content
Static pres-
oFF op1~
sure com-
op3
pensation
Night low
oFF op1~o
noise
p12
Overall de-
on
oFF
frost
ODU ad-
-
dress
Snow re-
oFF op1~
moval &
op3
rapid defrost
IDU capacity
on
oFF
adjusting
Target
oFF op1~
pressure
op3
adjusting
Comfort
on
oFF
Operation
* Functions save in EEPROM will be kept continuously, though the
system power was reset.

Group Number setting

Group Number setting for Indoor Units
- Confirm the power of whole system(Indoor Unit, Outdoor Unit) is
OFF, otherwise turn off.
- The communication cables connected to CEN.A and CEN.B terminal
should be connected to central control of Outdoor Unit with care for
their polarity (A-A, B-B ).
- Turn the whole system on.
- Set the group and Indoor Unit number with a wired remote control.
- To control several sets of Indoor Units into a group, set the group ID
from 0 to F for this purpose.
Outdoor Units (External PCB)
SODU.B SODU.A
IDU.B
IDU.A
CEN.B
B(D)
Example) Group number setting
1 F
Group Indoor unit
st
1
number indicate the group number
2nd number point out indoor unit number
SW04C ( : cancel)
SW03C ( : forward)
SW02C ( : backward)
SW01C (
: confirm)
SW01D (reset)
Value
Action
Display3 Content Display4 Implement Display5
Change
Selected
-
-
the set
Blank
the option
value
Change
Selected
-
-
the set
Blank
the option
value
Change
Selected
-
-
the set
Blank
the option
value
set
Change
-
0~255
the
the set
Blank
value
value
Change
Selected
-
-
the set
Blank
the option
value
Change
Selected
-
-
the set
Blank
the option
value
Change
Selected
-
-
the set
Blank
the option
value
Change
selected
-
-
the set
Blank
the option
value
CEN.A
DRY1
DRY2
GND
12V
A(C)
Group recognizing the central controller
Remarks
Save in
EEPROM
Save in
EEPROM
Save in
EEPROM
!
WARNING
Save in
• Valve address and central control address of its corresponding in-
EEPROM
door unit should be set identical in manual addressing.
Save in
EEPROM
EX)
Save in
EEPROM
HR unit
Save in
EEPROM
Save in
EEPROM

Static pressure compensation mode

This function secures the air flow rate of ODU, in case static pressure
has been applied like using duct at fan discharge of ODU.
Static pressure compensation mode setting method
Master unit PCB DIP switch on : No.5
Select the mode using '▶', '◀' Button :
"Func" Push the '●' button
Select the Function using '▶', '◀' Button :
"Fn2" Push the '●' button
Select the Option using '▶', '◀' Button :
"op1~op3" Push the '●' button
Start the Static pressure compensation mode :
Save the selected option value in EEPROM
FAN Maximum RPM of each step (220V Model)
Chassis
Max. RPM
FAN Maximum RPM of each step (460V Model)
Chassis
Max. RPM
No.0 group (00~0F)
No.1 group (10~1F)
No.2 group (20~2F)
No.3 group (30~3F)
No.4 group (40~4F)
No.5 group (50~5F)
No.6 group (60~6F)
No.7 group (70~7F)
No.8 group (80~8F)
No.9 group (90~9F)
No. A group (A0~AF)
No. B group (B0~BF)
No. C group (C0~CF)
No. D group (D0~DF)
No. E group (E0~EF)
No. F group (F0~FF)
Valve (04)
Indoor unit (04)
Valve (03)
Indoor unit (03)
Valve (02)
Indoor unit (02)
Valve (01)
Indoor unit (01)
Central control address
UX2
Standard
850
op1
870
op2
890
op3
900
UX2
Standard
730
op1
760
op2
780
op3
800
33
UX3
1050
1080
1110
1120
UX3
950
1020
1050
1130