INSTALLATION PROCESS
Indicate clearly who will be responsible for switch setting.
Determination of division work
Make connection clearly between outdoor, indoor,
Preparation of contract drawings
remote controller and option.
Take account of gradient
Sleeve and insert work
of drain piping
Check model name to
Installation of indoor unit
make sure the fitting
is made correctly
Special attention to dryness,
Refrigerant piping work
cleanness and tightness
Drain pipe work
Adjust to downward gradient
Make sure airflow is sufficient
Duct work
Make sure no gaps are left where
Heat insulation work
the insulating materials are joined
Electrical work
Multiple core cable must not be used.
(connection circuits and drive circuits)
(suitable cable should be selected)
In the final check for 24hours at 3.8 MPa(38.7 kgf/cm
Airtight test
must be no drop in pressure.
The vacuum pump used must have a capacity of reaching at least
Vacuum drying
5 torr, more than 1 hour
Recharge correctly as calculated in this manual. and record the
Additional charge of refrigerant
amount of added refrigerant
Make sure there are no gaps left between the facing materials
Fit facing panels
used on the ceiling
Refer to automatic addressing flowchart
Automatic addressing of indoor unit
Preheat the crank case with the electrical heater for more than 6 hours.
Run each indoor unit in turn to make sure the pipe work
Test run adjustment
has been fitted correctly
Explain the use of the system as clearly as possible to your customer and
Transfer to customer with explanation
make sure all relevant documentation is in order
!
CAUTION
• The above list indicates the order in which the individual work
operations are normally carried out but this order may be varied
where local conditions warrants such change.
• The thickness of the piping should comply with the relevant
local and national regulations for the designed pressure 3.8MPa.
• Since R410A is a mixed refrigerant, the required additional re-
frigerant must be charged in its liquid state.(If the refrigerant is
charged in its gaseous state, its composition changes and the
system will not work properly.)
OUTDOOR UNITS INFORMATION
!
CAUTION
Combination Ratio(50~200%)
Outdoor Number
Single outdoor units
Double outdoor units
Triple outdoor units
Notes : * We can guarantee the operation only within 130%
Combination. If you want to connect more than 130%
combination, please contact us and discuss the re-
quirement like below.
• If the operation of indoor unit is more than 130%, the airflow is
operated as low in the all indoor units.
Outdoor unit foundation work
The foundation must be level even
Installation of outdoor unit
Avoid short circuits and ensure
sufficient space is allowed for service
2
) there
Connection Ratio
200%
160%
130%
Power Supply : 220-240 V3~ 50Hz / 220 V3~ 60Hz
Model Name : ARUB***BTE4
Unit
HP
8
Combination Unit
ARUB080BTE4
ARUB080BTE4
Model Name
Independ-
ent Unit
kg
7.7
Refigerant charging
amount
lbs
16.9
Number of maxmum connectable indoor units
13(20)
kg
195 × 1
Net Weight
lbs
430 × 1
mm
(920×1,680×760)×1 (920×1,680×760)×1 (920×1,680×760)×1
Dimensions
(WxHxD)
inch
(36.2×66.1×29.9)×1 (36.2×66.1×29.9)×1 (36.2×66.1×29.9)×1
Liquid Pipes mm(inch)
9.52(3/8)
Pipe
Connc-
Low Pressure Gas Pi p es mm(inch)
19.05(3/4)
tions
Hi g h Pressure Gas Pi p es mm(inch)
15.88(5/8)
Unit
HP
14
Combination Unit
ARUB140BTE4
ARUB140BTE4
Model Name
Independ-
ent Unit
kg
10.7
Refigerant charging
amount
lbs
23.6
Number of maxmum connectable indoor units
23(35)
kg
245 x 1
Net Weight
lbs
540 × 1
mm
(1,240×1,680×760)×1 (1,240×1,680×760)×1 (1,240×1,680×760)×1
Dimensions
(WxHxD)
inch
(48.8×66.1×29.9)×1 (48.8×66.1×29.9)×1 (48.8×66.1×29.9)×1
Liquid Pipes mm(inch)
12.7(1/2)
Pipe
Connc-
Low Pressure Gas Pi p es mm(inch)
28.58(1 1/8)
tions
Hi g h Pressure Gas Pi p es mm(inch)
22.2(7/8)
Unit
1 Outdoor Unit
HP
20
Combination Unit
ARUB200BTE4
ARUB200BTE4
Model Name
Independ-
ent Unit
kg
10.7
Refigerant charging
amount
lbs
23.6
Number of maxmum connectable indoor units
32(50)
kg
285 × 1
Net Weight
lbs
628 × 1
mm
(1,240×1,680×760)×1 (920×1,680×760)×2 (920×1,680×760)×2
Dimensions
(WxHxD)
inch
(48.8×66.1×29.9)×1 (36.2×66.1×29.9)×2 (36.2×66.1×29.9)×2
Liquid Pipes mm(inch)
15.88(5/8)
Pipe
Connc-
Low Pressure Gas Pi p es mm(inch)
28.58(1 1/8)
tions
Hi g h Pressure Gas Pi p es mm(inch)
22.2(7/8)
Unit
HP
26
Combination Unit
ARUB260BTE4
ARUB140BTE4
Model Name
Independ-
ARUB120BTE4
ent Unit
kg
10.7 × 1 + 7.7 × 1
Refigerant charging
amount
lbs
23.6 × 1 + 16.9.0 × 1 23.6 × 1 + 16.9.0 × 1 23.6 × 1 + 16.9.0 × 1
Number of maxmum connectable indoor units
42(52)
kg
245 × 1 + 208 × 1
Net Weight
lbs
540 × 1 + 459 × 1
(1,240×1,680×760)×1
mm
+ (920×1,680×760)×1
Dimensions
(WxHxD)
(48.8×66.1×29.9)×1
inch
+(36.2×66.1×29.9)×1
Liquid Pipes mm(inch)
19.05(3/4)
Pipe
Connc-
Low Pressure Gas Pi p es mm(inch)
34.9(1 3/8)
tions
Hi g h Pressure Gas Pi p es mm(inch)
28.58(1 1/8)
1 Outdoor Unit
10
12
ARUB100BTE4
ARUB120BTE4
ARUB100BTE4
ARUB120BTE4
7.7
7.7
16.9
16.9
16(25)
20(30)
208 × 1
208 × 1
459 × 1
459 × 1
9.52(3/8)
12.7(1/2)
22.2(7/8)
28.58(1 1/8)
19.05(3/4)
19.05(3/4)
1 Outdoor Unit
16
18
ARUB160BTE4
ARUB180BTE4
ARUB160BTE4
ARUB180BTE4
10.7
10.7
23.6
23.6
26(40)
29(45)
245 x 1
285 × 1
540 × 1
628 × 1
12.7(1/2)
15.88(5/8)
28.58(1 1/8)
28.58(1 1/8)
22.2(7/8)
22.2(7/8)
2 Outdoor Unit
22
24
ARUB220BTE4
ARUB240BTE4
ARUB120BTE4
ARUB120BTE4
ARUB100BTE4
ARUB120BTE4
7.7 × 2
7.7 × 2
16.9 × 2
16.9 × 2
35(44)
39(48)
208 × 2
208 × 2
459 × 2
459 × 2
15.88(5/8)
15.88(5/8)
34.9(1 3/8)
34.9(1 3/8)
28.58(1 1/8)
28.58(1 1/8)
2 Outdoor Unit
28
30
ARUB280BTE4
ARUB300BTE4
ARUB160BTE4
ARUB180BTE4
ARUB120BTE4
ARUB120BTE4
10.7 × 1 + 7.7 × 1
10.7 × 1 + 7.7 × 1
45(56)
49(60)
245 × 1 + 208 × 1
285 × 1 + 208 × 1
540 × 1 + 459 × 1
628 × 1 + 459 × 1
(1,240×1,680×760)×1
(1,240×1,680×760)×1
+ (920×1,680×760)×1
+ (920×1,680×760)×1
(48.8×66.1×29.9)×1
(48.8×66.1×29.9)×1
+(36.2×66.1×29.9)×1
+(36.2×66.1×29.9)×1
19.05(3/4)
19.05(3/4)
34.9(1 3/8)
34.9(1 3/8)
28.58(1 1/8)
28.58(1 1/8)