Group Number Setting; Cool & Heat Selector - LG multi V ARUV160DTS4 Installation Manual

Table of Contents

Advertisement

26
CAUTION
!
• In replacement of the indoor unit PCB, always perform Automatic
addressing setting again (At that time, please check about using In-
dependent power module to any indoor unit.)
• If power supply is not applied to the indoor unit, operation error occur.
• Automatic Addressing is only possible on the master Unit.
• Automatic Addressing has to be performed after 3 minutes to im-
prove communication.
The Procedure of Automatic Addressing
Power On
Waiting 3 minutes
Press RED Button for 5 sec.
(SW01C)
Automatic addressing start
7-segment LED
= 88
Don't press RED Button
(SW01C)
• Automatic addressing setting end
Numbers of indoor unit connection set whose
addressing is completed are indicated for 30seconds
Waiting about 2~7 minutes
on 7-segment LED after completing setting
NO
7-segment LED
= 88
YES
Indoor address number is displayed on wired remote control or
indoor unit display window. It is not an error message, will
disappeared when on/off button is pressed on remote control
ex) Display of 01, 02, ..., 15 means connection of 15 indoor units
OK
and Automatic addressing is completed normally.
Setting the function
Select the mode/function/option/value using '▶', '◀' Button and con-
firm that using the '●' button after dip switch No.5 is turned on.
DIP-SW01 7 - Segment
Mode
Function
Option
Content Display1
Content
Display2
Content
Cool & Heat
oFF op1~
Selector
op2
Static pres-
oFF op1~
sure com-
op3
pensation
Night low
oFF op1~o
noise
p12
Overall de-
on
oFF
frost
ODU ad-
-
dress
Snow re-
oFF op1~
moval &
op3
rapid defrost
IDU capacity
on
oFF
adjusting
Target
oFF op1~
pressure
op3
adjusting
Comfort
on
oFF
Operation
* Functions save in EEPROM will be kept continuously, though the
system power was reset.
* Fn4 and Fn6 are not applicable to cooling only models
Check the connections
of communication cable
SW04C ( : cancel)
SW03C ( : forward)
SW02C ( : backward)
SW01C (
: confirm)
SW01D (reset)
Value
Action
Remarks
Display3 Content Display4 Implement Display5
Change
Selected
Save in
-
-
the set
Blank
the option
EEPROM
value
Change
Save in
Selected
-
-
the set
Blank
the option
EEPROM
value
Change
Selected
Save in
-
-
the set
Blank
the option
EEPROM
value
Change
Save in
Selected
-
-
the set
Blank
the option
EEPROM
value
set
Change
Save in
-
0~255
the
the set
Blank
EEPROM
value
value
Change
Save in
Selected
-
-
the set
Blank
the option
EEPROM
value
Change
Save in
Selected
-
-
the set
Blank
the option
EEPROM
value
Change
Save in
Selected
-
-
the set
Blank
the option
EEPROM
value
Change
Save in
selected
-
-
the set
Blank
the option
EEPROM
value

Group Number setting

Group Number setting for Indoor Units
- Confirm the power of whole system(Indoor Unit, Outdoor Unit) is
OFF, otherwise turn off.
- The communication cables connected to CEN.A and CEN.B terminal
should be connected to central control of Outdoor Unit with care for
their polarity (A-A, B-B ).
- Turn the whole system on.
- Set the group and Indoor Unit number with a wired remote control.
- To control several sets of Indoor Units into a group, set the group ID
from 0 to F for this purpose.
Outdoor Units (External PCB)
SODU.B SODU.A
IDU.B
IDU.A
CEN.B
B(D)
Example) Group number setting
1 F
Group Indoor unit
st
1
number indicate the group number
2nd number point out indoor unit number
Group recognizing the central controller
No.0 group (00~0F)
No.1 group (10~1F)
No.2 group (20~2F)
No.3 group (30~3F)
No.4 group (40~4F)
No.5 group (50~5F)
No.6 group (60~6F)
No.7 group (70~7F)
No.8 group (80~8F)
No.9 group (90~9F)
No. A group (A0~AF)
No. B group (B0~BF)
No. C group (C0~CF)
No. D group (D0~DF)
No. E group (E0~EF)
No. F group (F0~FF)
Cool & Heat selector
Mode setting method
Master unit PCB DIP switch on : No.5
Select the mode using '▶', '◀' Button :
"Func" Push the '●' button
Select the Function using '▶', '◀' Button :
"Fn1" Push the '●' button
Select the Option using '▶', '◀' Button :
"oFF","op1","op2" Push the '●' button
Cool & Heat Selection mode is set
Function setting
Switch control
Switch(Phase) Switch(Bottom)
Right
Left
Not operate
Right
Right
Not operate
Left
-
Not operate
CEN.A
DRY1
DRY2
GND
12V
A(C)
Function
oFF
op1(mode)
op2(mode)
Cooling
Cooling
Heating
Heating
Fan mode
Off

Advertisement

Table of Contents
loading

Table of Contents