Installation Guide
DOC.IG.BQC44.1 Rev. 1
11.2.4 Wiring instructions QC44.xP1Nxx1
Intrinsically safe Control Module with the switch
types M and G where * is M or G
Unclassified or Non
Hazardous Location
Terminal connections
Solenoid 1
IS Approved Barrier
Solenoid 2*
IS Approved Barrier
* Solenoid 2 only available with
Fail in Last Position function
Cable range:
Solid / Stranded wire:
0.2-2.5mm2 or 30-12 AWG
Table 11.5
Notes:
Installation must be inaccordance
1
with:
2
Before operation:
3
Barriers:
4
Intrinsically safe equipement
Barrier I.S. Entity Parameters must
5
meet the following conditions:
6
When multiple barriers are used:
Hazardous or
Classified Location
-
+
-
+
CSA
Canadian Electrical Code,
Part1
The control module in combination with the pneumatic module must be mounted
Must be CSA approved and installed in an enclo-
sure that meets the requirements of CEC part1. Must be certified by an European Noti-
Control equipment connected to the barrier
must not use or generate more than 250Vrms
or Vdc.
Must be CSA Approved
Uo =< Ui
Io =< Ii
Co >= Ci + C cable
* Each I.S. Circuit must use shielded, twisted pairs
* Cable insulation and shielding must extend to within paritioned area of terminals
7
8
9
10
11
12
1
2
3
4
5
6
-
-
+
+
IS Approved
IS Approved
Barrier
Barrier
Switch 1
Switch 2
properly on the actuator.
Lo >= Li + L cable
Bettis Q-Series
February 2017
Hazardous or
Classified Location
Unclassified or Non
Hazardous Location
ATEX
The national wiring practices of the
country of use
fied body and installed per manufac-
turer's installation instructions.
Must be ATEX Approved
Po =< Pi