V-FloFan
Fault
Fan rotates in wrong direction
Fan speed (rpm) is too low
High power consumption
Unusual or excessive noises
The desired airflow pattern Is not obtained
Use original spare parts only.
9

End of life

Disposal
At the end of the life of this fan, dispose of it properly in accordance with
regulations that apply in your area.
NOTICE
Always sort and recycle waste.
Recycling
The main materials used in the electric motor are copper, steel and
aluminium.
Most of the fan parts have the recycling symbol with material code listed on
them to facilitate proper recycling. Some parts are made of easy to identify
materials such as steel, and have no recycling symbol on them.
Symbol Material
Polypropylene
ABS (Acrylonitrile butadiene styrene)
Polyamide
INS00003-B
Original instructions
Possible cause
Only for 1~ motors: wrong or defective capacitor
1~ fan motors: capacitor incorrectly connected
3~ fan motors: power supply incorrectly connected
Supply voltage too low
Incorrect supply frequency
Only for 1~ fans: wrong or defective capacitor
Only for 3~ fans: STAR instead of DELTA connec-
ted
3~fan motors: Phase failure
Fan overloaded
Fan speed too high
Bearings damaged or worn
Impeller hits fan housing
Fan is operating in stall point
Bearings damaged or worn
Other air currents influence the airflow pattern
Symbol Material
10

EU Declaration of Conformity

(according to Annex II.1.A. of the machinery directive 2006/42/EC)
The manufacturer: Vostermans Ventilation B.V.
Visiting address:
Postal address:
Telephone:
Fax:
Internet:
E-mail:
declares under sole responsibility that the following machineries:
Name / description: V-FloFan
Article numbers starting with:
T4D40, T6D40
Possible remedy
Replace capacitor
Connect according to wiring diagram (contact sup-
plier)
Swap any 2 of the 3 phases of the power supply
Check power supply
Check power supply
Replace capacitor
Connect as DELTA
Check wiring diagram!
Restore all 3 phases
Check for overloading of fan system (intake or ex-
haust blocked?)
Check supply voltage and frequency
Replace bearings
Check installation and fixings and alignment
Lower system resistance
(Intake or exhaust blocked)
Replace bearings
Check if all windows and doors are closed
Check is other air currents affect the operation of
the V-FloFan , optionally by means of a smoke gen-
erator.
Glass fibre reinforced polypropylene
Aluminium
EU Declaration of Conformity
Industrial Zone Venlo 5082
Parlevinkerweg 54
NL-5928 NV Venlo
The Netherlands
P.O. Box 3025
NL-5902 RA Venlo
The Netherlands
+31 (0) 77 389 32 32
+31 (0) 77 382 08 93
www.vostermans.com