15 Attachment - using devices at altitudes greater than 2000 m above sea level
22
Example calculation for 3000 m
The following calculation and the illustrated derating curve are
provided as examples.
Perform the actual calculation and offset the derating curve for
the device used according to the technical data and the
"Derating" section.
Figure 13: Example of a suspended derating curve (red)
27 °C x 0,906 = 24 °C
55 °C x 0,906 = 49 °C
ESR5-NO-41-24VAC-DC 12/19 MN049009EN www.eaton.com