Introduction Thank you for purchasing the TLV pneumatic control valve. This product has been thoroughly inspected before being shipped from the factory. When the product is delivered, before doing anything else, check the specifications and external appearance to make sure nothing is out of the ordinary.
The three types of cautionary items above are very important for safety: be sure to observe all of them as they relate to installation, use, maintenance and repair. Furthermore, TLV accepts no responsibility for any accidents or damage occurring as a result of failure to observe these precautions.
Page 5
When using this product, NEVER stand close to, or leave tools anywhere near, moving parts, such as the shaft. Contact with moving parts or objects becoming caught in moving parts could lead to injury or damage or other accidents. 172-65587MA-02 (CV-COSR Pneumatic Control Valve) 3 Jun 2019...
Page 7
Less than 0.01% of the rated Cv and Kvs value (Leak Rate Class) (IEC/ANSI/EN Class IV) Condensate Drainage Rc(PT) , BSPT or NPT Port (1 MPa = 10.197 kg/cm *Do not use for toxic, flammable or otherwise hazardous fluids. 172-65587MA-02 (CV-COSR Pneumatic Control Valve) 3 Jun 2019...
24 Bolt 25 Nut 26 Stem Bracket Connector Plate Set 27 Cover Bolt 28 Drain Plug *Replacement parts are available only in the following kits: M = Maintenance Kit R = Repair Kit 172-65587MA-02 (CV-COSR Pneumatic Control Valve) 3 Jun 2019...
1. Blowdown Before installing the CV-COSR unit, be sure to blow down all piping thoroughly. If this is not possible, perform a blowdown using the bypass valve. Blowdown is especially important for newly installed piping or after the system has been shut down for a long period of time.
Page 10
9. Shut-off Valve Installation Though the CV-COSR adequately performs the function of a shut-off valve initially, extended use will result in a drop in its performance as an isolation valve. Be sure to install a separate shut-off or automatic valve if complete isolation is needed.
Page 11
If air quality results in operation failure, the entire actuator unit (including the integrated positioner) must be replaced. If there is a problem in operation, determine the cause using the “Troubleshooting” section in this manual. 172-65587MA-02 (CV-COSR Pneumatic Control Valve) 3 Jun 2019...
7. Retighten the screw (1) in the center section of the electrical wiring plug connector by using a screwdriver. Connector Screw NOTE: Use shielded cable to avoid noise interference in the electrical wiring. 172-65587MA-02 (CV-COSR Pneumatic Control Valve) 3 Jun 2019...
3. Turn on the power to the controller operation signal source, etc. (referred to hereinafter as the controller). 4. Set the operation signal output from the controller to the CV-COSR to 0% (4 mA). 5. Check the CV-COSR valve travel and the actuator air supply pressure.
Page 14
11. After completing the adjustment, insert the jumper pin securely into their previous position and close the cover. Stroke Guide Zero/Span Adjustment Jumper Pin Span Adjustment Stroke Gauge Potentiometer 100% Cover Plate Zero Adjustment Dial 172-65587MA-02 (CV-COSR Pneumatic Control Valve) 3 Jun 2019...
Readjust the air pressure valve travel differ from the reducing valve and positioner designated operation signal value? zero and span; if that does not solve the problem, refer to the "Troubleshooting" section 172-65587MA-02 (CV-COSR Pneumatic Control Valve) 3 Jun 2019...
Remove with an open-end Consult the table of tightening Bonnet Nut wrench torques and tighten to the proper torque Be careful not to pinch your fingers between the CAUTION valve stem and actuator stem! 172-65587MA-02 (CV-COSR Pneumatic Control Valve) 3 Jun 2019...
Page 17
Replace with a new gasket if warped or Gasket surfaces damaged Bolt Flange Valve Bonnet Guide Gasket Guide Bushing Valve Bonnet Valve Plug & Stem Valve Bonnet Gasket Valve Seat Valve Bonnet Valve Seat Gasket Guide Body 172-65587MA-02 (CV-COSR Pneumatic Control Valve) 3 Jun 2019...
Page 18
Spring grease; reattach the V-rings Valve Bonnet with their grooves facing downward Stuffing Box Pull up and out Reinsert Washer Sectional View of Stuffing Box V-rings Stuffing Box Spring 172-65587MA-02 (CV-COSR Pneumatic Control Valve) 3 Jun 2019...
Page 19
40* (29*) N·m (lb·ft) 14 ( ) mm (in) (1 N·m ≈ 10 kg·cm) * These values represent tightening torques for threads that are wrapped with 3 - 3.5 turns of sealing tape. 172-65587MA-02 (CV-COSR Pneumatic Control Valve) 3 Jun 2019...
Inspect the controller and signal system controller is emitting a 4 to 20 repair the signal wiring if mA signal and that the wires necessary are not disconnected, etc. Continued on next page 172-65587MA-02 (CV-COSR Pneumatic Control Valve) 3 Jun 2019...
Page 21
Clean the filter or replace with clogged a new filter Valve travel is The setting of the Check the set value based on Adjust the controller's setting the controller’s PID parameters unstable controller is faulty values 172-65587MA-02 (CV-COSR Pneumatic Control Valve) 3 Jun 2019...
One year following product delivery. 2. Warranty Coverage TLV CO., LTD. warrants this product to the original purchaser to be free from defective materials and workmanship. Under this warranty, the product will be repaired or replaced at our option, without charge for parts or labor.