System Sensor i3 Series Installation And Maintenance Instructions page 3

Reversing relay/synchronization module

Advertisement

Figure 4. 4-Wire system triggered from alarm relay contact:
UL LISTED
ALARM
CONTROL
PANEL
ALARM
RELAY
(NO Contact)
+
DETECTOR
POWER
+
AUX POWER
OR
DETECTOR
POWER
+
INITIATING
DEVICE
CIRCUIT
Connection Diagrams with Ademco Vista Panels
The connection diagrams enclosed show how to connect the 2WTA-B model smoke detector to the Vista panels using the
System Sensor polarity reversal relay module (RRS-MOD). Please make sure that the smoke detectors are connected prop-
erly to the zones specified in the wiring diagrams for proper operation of the smoke detectors.
Figure 5. Connecting 2WTA-B smoke detectors to Ademco controls using RRS-MOD module triggered from
bell/alarm circuit:
SYSTEM SENSOR REVERSING
RELAY/SYNCHRONIZATION
UL LISTED
MODULE ( RRS-MOD)
ALARM
CONTROL
(MOUNT INSIDE CONTROL ENCLOSURE)
PANEL
BELL/
ALARM
PURPLE
CIRCUIT
T+
(positive signal
in alarm state)
ADEMCO
CONTROL
PANEL
APPCLICABLE
YELLOW
2 -WIRE
+
CONTROLS:
INITIATING
VISTA-20
CIRCUIT
ORANGE
VISTA-40
VISTA-50P
VISTA-32FB
VISTA-100
VISTA-128FB
RED
+
AUX POWER
BLACK
*470Ω 1/2 WATT RESISTOR NEEDED FOR PANEL TO RESET
Figure 6. Connecting 2WTA-B smoke detectors to Ademco controls using RRS-MOD module triggered from
auxiliary relay:
UL LISTED
WHEN 5100XM JUMPER W3 INTACT
ALARM
CONTROL
PANEL
AUXILIARY
RELAY
PURPLE
T +
ADEMCO
CONTROL
PANEL
YELLOW
+
APPCLICABLE
2 – WIRE
CONTROLS:
SMOKE
ORANGE
5110XM
ZONE
5140XM
VISTA-32FB
VISTA-100
VISTA-128FB
RED
+
AUXILIARY
POWER
OUTPUT
BLACK
TAKE POWER FROM CONTROLS
AUXILIARY POWER OUTPUT ONLY
D500-44-00
PURPLE
T+
BROWN
OUT+
YELLOW
IN+
ORANGE
IN–
WHITE
OUT–
RED
PWR+
BLACK
PWR–
BROWN
WHITE
+
OPTIONAL
SYSTEM SENSOR
REMOTE
2WTA-B SMOKE
470
ANNUNCIATOR
DETECTORS
1/2 WATT*
(RA400Z)
(UP TO 16 DETECTORS
PER ZONE)
NOT REQUIRED ON 5110XM
SYSTEM SENSOR REVERSING
RELAY/SYNCHRONIZATION MODULE (RRS-MOD)
(MOUNT INSIDE CONTROL ENCLOSURE)
BROWN
WHITE
+
SYSTEM SENSOR
OPTIONAL
2WTA-B SMOKE
REMOTE
470
DETECTORS
ANNUNCIATOR
1/2 WATT*
(UP TO 16 DETECTORS
(RA400Z)
PER ZONE)
*470Ω 1/2 WATT RESISTOR NEEDED FOR PANEL TO RESET
1 + IN
2 + OUT
3 - IN/OUT
4 N.O.
5 C
1 + IN
1 + IN
2 + OUT
2 + OUT
3 - IN/OUT
3 - IN/OUT
4 N.O.
4 RA+
5 C
5 C
+
OPTIONAL
REMOTE
ANNUNCIATOR
(RA400Z)
1 + IN
1 + IN
2 + OUT
2 + OUT
3 - IN/OUT
3 - IN/OUT
4 RA+
4 RA+
5 RA-
5 RA-
+
OPTIONAL
REMOTE
ANNUNCIATOR
(RA400Z)
3
EOL RELAY
(SHOWN ENERGIZED
1 + IN
2 + OUT
3 - IN/OUT
4 N.O.
5 C
EOL
Programming information:
• The supervisory feature for the
EOL
2K OHMS
bell circuit must be turned off.
See applicable control manual
for procedure.
RRS-MOD Configuration:
• Set switch on RRS-MOD to "OFF".
Programming information:
• Program Auxiliary relay to acti-
EOL
2K OHMS
vate on alarms
• Assign Auxiliary relay as an
output for zones programmed
for fire alarm response only
(Types 9, 16, or 17)
RRS-MOD Configuration:
• Set switch on RRS-MOD to "ON".
S0104-00
S0105-01
S0106-01
I56-2203-003