Fault Handling

7-1. Fault Alarm Table

If the controller and the control panel are faulty, the code "EE/ED" will be displayed.
No.
Input Port
1
TH1
No.1 analog sensor fault (water inlet temperature)
2
TH2
No.2 analog sensor fault (water outlet temperature)
3
TH3
No.3 analog sensor fault (suction temperature A)
4
TH4
5
TH5
No.5 analog sensor fault (discharge temperature A-1)
6
TH6
No.6 analog sensor fault (discharge temperature A-2)
7
TH7
No.7 analog sensor fault (ambient temperature)
8
TH8
No.8 analog sensor fault (suction temperature B)
9
TH9
10
TH10
No.10 analog sensor fault (discharge temperature B-1)
11
TH11
No.11 analog sensor fault (discharge temperature B-2)
12
TH12
No.12 analog sensor fault (total water outlet temperature)
13
CN13
14
CN14
15
IND3
16
IND4
17
IND5
18
IND6
19
IND8
20
IND9
21
CN13
22
CN14
TH1,TH2
23
and
TH1TH2
24
TH3, TH8
25
CN13
26
CN14
27
CN15
28
CN16
29
TH7
The ambient temperature exceeds the working range
30
CN29
Communication fault between control panel and modular controller
31
CN4/XP1
Communication fault between single unit controller and mainboard
TH5/TH6/
32
TH10/TH11
33
--
34
--
Note: The faults in this table are only displayed on the single unit controller and the modular controller.
Note 1: When this fault occurs, switch off all compressors. The water pump will continuously operate.
Note 2: Lock "antifreezing locking time of plate type heat exchanger for refrigeration unit". the fault is permitted to be manually reset only when
the water temperature is recovered to the normal state.
Note 3: This alarm code will be displayed only when "module control" is selected. Note 4: This alarm code will be displayed only when
"module control" is selected and it is a host unit (A0).
In case of fault, the controller and the centralized controller will show corresponding fault code and conduct fault handling, the alarm output
relay will be closed.
When all the fault input terminals are disconnected, it means fault alarm; when all the fault input terminals are closed, it means normal.
After the fault is cleared, the system will maintain fault status (to remind user for unit inspection). The system will restore the operating status
before the fault only after user press the "Reset" key (only reset one fault at a time in case of multiple faults) or restart the unit.
All the faults must be reset manually.
Fault Description
No.4 analog sensor fault
No.9 analog sensor fault
No.13 analog sensor fault (suction pressure A)
No.14 analog sensor fault (suction pressure B)
High-pressure switch of system B
High-pressure switch of system A
Water flow switch alarm
Overload of water pump
Overload of compressor A-1 or A-2
Overload of compressor B-1 or B-2
Low-pressure of system A
Low-pressure of system B
Refrigeration antifreezeing alarm
Abnormal suction temperature
Low pressure overrun of system A
Low pressure overrun of system B
High pressure overrun of system A
High pressure overrun of system B
Abnormal discharge temperature
Inlet and outlet of water pipe is reversed
Configuration error of model
Code of
Code of
Single Unit
Centralized
Controller
Controller
20
20
21
21
22
22
23
23
24
24
25
25
26
26
27
27
28
28
29
29
2A
2A
2B
2B
2C
2C
2D
2D
H2
65
H1
65
FL
6D
OP
6A
C1
68
C2
69
L1
66
L2
67
Switch off all compressors. The water
E3
8D
pump continuously operates.
E4
91
The water pump continuously operates.
Switch off the compressor of the system A.
78
78
If this fault occurs twice, switch off and give
Switch off the compressor of the system B.
7A
7A
If this fault occurs twice, switch off and give
Switch off the compressor of the system A.
2E
2E
If this fault occurs twice, switch off and give
Switch off the compressor of the system B.
2F
2F
If this fault occurs twice, switch off and give
87
87
ED
--
--
EE
AC/AD/ AE/
AC/AD/ AE/
AF
AF
A0
A0
E1
E1
Fault Handling
Fault Handling
Turn off devices
Turn off devices
Turn off devices
Turn off devices
Turn off devices
Turn off devices
Turn off devices
Turn off devices
2
Turn off devices
2
Turn off devices
2
Turn off devices
2
Turn off devices
4
Turn off devices
Turn off devices
2
Turn off devices
2
Turn off devices
Turn off devices
Turn off devices
Turn off devices
Turn off devices
2
Turn off devices
Turn off devices
2
1
Switch off all compressors.
12
an alarm.
an alarm.
an alarm.
an alarm.
Turn off devices
Turn off devices
2
Turn off devices
Turn off devices
Turn off devices
Turn off devices
37