Viavi T-BERD 5800 Quick Card page 3

Network tester, monitoring ds1 signals at a digital cross connect panel
Hide thumbs Also See for T-BERD 5800:

Advertisement

11. Using the drop-down menus, select
"Rx 2/Interface/Signal" for the right
results display.
12. Verify the following:
• Rx 2 Summary LED is green
• Rx 2 Signal Present LED is green
• Rx 2 Frame Sync LED is green
• Rx 2 Rx Frequency (Hz) = 1544000  50 Hz
• BPVs = 0
• Rx 2 Frame Slips = 0
Troubleshooting tips:
If no Signal Present, check cables and verify you are in correct monitor point. Check the Rx Input
settings (DSX Mon or Bridge)
If no Frame Sync, check Framing setting (ESF or D4).
If Rx Frequency ≠ 1544000  50 Hz, there is no clock on the circuit.
If BPVs present, there is an issue with either the signal level (Rx input settings, bad cable, etc.) or a
circuit problem between the test set and the last intelligent piece of equipment that is transmitting the
signal to the test set.
If CRC Errors, Framing Errors, or other errors present, check the Rx Input setting (DSX Mon or Bridge)
If errors persist, perform intrusive testing (BERT) to isolate the issue.