Parameter Table - Helios EDR Installation And Operation Manual

Electronic pressure controller
Table of Contents

Advertisement

Available languages

Available languages

Installation and Operating Specification EDR

7.5 Parameter table

Parameter
Display / factory setting
Mode
Δp
(0.000 in.wg)
Setpoint 1
Uout
EDR
SETTING
Setpoint 1
Setpoint 2
Pband
Min. Uout
Max. Uout
Mode
metric: Pa, m
Units
inch: in.wg, cfm, K-Factor US
1: 0...1000 Pa
2: 0...500 Pa
Measuring
Range
3: 0...300 Pa
4: 0...200 Pa
Autozero
Offset
1 Setting range:
2 small value = quick regulation, great value = slow regulation (high stability)
- Parameter for selected mode not available
(xxx)
Values for Imperial units (US)
L-BAL-E292-GB 1841 Index 001
4.00
INFO
0 Pa
(0.000 in.wg)
-
(2.0 in.wg)
0.0 V
2.10
4.01
+
5.01
-
(2.0 in.wg)
-
(2.0 in.wg)
-
(2.0 in.wg)
-
-
BASE SETUP
4.00
3
/h, K-Factor
(0...4.0 in.wg)
(0...2.0 in.wg)
(0...1.2 in.wg)
(0...0.8 in.wg)
OFF => ON
0 Pa
(0.000 in.wg)
4.01
: 0...100 % sensor measuring range
Mode
4.01
Information
0 Pa
Display actual value for differential pressure
500 Pa
Display active Setpoint
9.9 V
Magnitude of the output voltage 0...10 V
2.10
Software version
Setting
500 Pa
Setpoint 1
500 Pa
Setpoint 2
(active if voltage at terminals 1, 2)
500 Pa
Pband
Min. output voltage: 0.0...10.0 V (priority
0.0 V
over "Max. Uout")
10.0 V
Max. output voltage: 10.0...0.0 V
Base setup
Mode
4.01
SI units or Imperial units (US)
Adjustable measuring range
Automatic "0" offset
Sensor offset (automatically when "Auto-
zero")
Setting range: +/ - 1000 Pa
in.wg)
Part.-No.
10/15
Programming
Funktion
1
1
1, 2
(+/- 4.000

Advertisement

Table of Contents
loading

This manual is also suitable for:

01437

Table of Contents