Waterproof self testing maintained emergency led luminaires

Advertisement

Back Up Operation
The autonomous duration of battery during
emergency mode is at least the one that is
stated
in
the
characteristics. During emergency mode, a
light source test is also performed.
Resetting Errors
Place the test card A-1900 on the side of the
indications (page 4) and remove it after the
reset is conducted (the indications light in
sequence), to delete all the indicated LED
errors. Then the luminaire enters regular
operation mode.
Indication LED status (with connected
mains power supply).
Charge
On: Good charge current.
Οff: No battery (No charging current
or disconnected battery).
Lamp Fault (with L1 connected to L)
Οn (with LED strip off): Faulty LED strip
(must be replaced).
Οn (with LED strip on): Problem in the back
up circuit of the LED strip (must be checked
by an authorized personnel).
Off: Good LED strip.
Battery Fault
Οff: Battery OK.
Blink (With Charge LED ON): Autonomy or
low battery problem (the battery must be
replaced).
Blink (With Charge LED Off): No charging
current or disconnected battery.
ΑΤΤΕΝΤΙΟΝ!!!
1. Operations for installation, maintainance or
testing must be done by authorized personnel
only, after a mains interruption.
1. Remove the front cover by unscrewing the retaining screws. Remove the acrylic plate.
2. Always use in any case round mains cable, with a diameter of 12-14mm (H05RN-F type
4x1mm² or any other type, at least equal to it's mechanical and electrical properties).
ATTENTION!! The cable must not be deformed in any way (This requirement is important
to ensure the tightness isolation IP 65). Pass the round cable through the cable gland and
tighten it all the way.
3. Unfasten the screw to remove the plastic cap (photo1) and connect the battery's cable as
shown in the photo 2. Replace the plastic cap and fasten the retaining screw.
4. Connect the mains cables as shown in figures 5 and 6. Yellow wire to GND, blue to N, brown
to L and black for maintained operation. The black wire can be connected to an external switch
to control the maintained or non maintained operation of the luminaire. For permanent
maintained operation use three wires to power the luminaire, GΝD for ground N for neutral, L for
live wire and link the brown and black wire to the same terminal.
5. Refit the acrylic plates and the front cover by srewing the removed screws in step 1.
6. Power on the device.
Page 2 from 4
list
of
the
technical
INSTALLATION INSTRUCTIONS
2. The device must be connected to the
m a i n s p o w e r s u p p l y t h r o u g h a f u s e
dependent on the total amount of the line's
power load.
3.
In case of battery or lamp replacement,
these must be replaced by parts of the same
type, by the manufacturer or by a competent
person.
4. In case of inactive use for a period greater
than 2 months, disconnect the batteries by
pulling out the battery's connectors.
5. I s not allowed to discard batteries in
t i
to common trash bins, they must be
discarded only
points. Do not incinerate.
INSTALLATION
To install the luminaire follow the installation
instructions below.
NOTE: LED= Light Emitting Diode
LABELING EXPLANATION:
X: Self contained
1: Maintained (*)
A: Including test device
G: Internally illuminated
*90: 1.5 hour duration
180: 3 hour duration
(*) Maintained operation: The luminaire lights
its illumination source, when it is powered by
the mains power supply or not.
Non Maintained operation: The luminaire
lights its illumination source, only in power
supply's failure.
The light source contained in this
luminaire shall only be replaced by the
manufacturer, or his agent, or a similar
qualified person.
NOTE! The light source is non-user
replaceable.
in battery recycling
923579000_09_003