Download Print this page
olympia electronics GR-579/L/90/WP Manual

olympia electronics GR-579/L/90/WP Manual

Waterproof self testing maintained emergency led luminaires

Advertisement

Quick Links

WATERPROOF SELF TESTING MAINTAINED EMERGENCY LED LUMINAIRES
TECHNICAL CHARACTERISTICS
(for LED MODULE Specs. see page 4)
OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERIES (Ni-Cd)
BATTERY PROTECTION
INDICATIONS - CONTROLS
CHARGING TIME
MINIMUM AUTONOMOUS DURATION
ILLUMINATION SOURCE
LIGHT SOURCE INTENSITY (230V AC/emerg.)
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
CONSTRUCTION MATERIALS
EXTERNAL DIMENSIONS
TYPICAL WEIGHT
GUARANTEE
GENERAL
These luminaires are used in places where
emergency luminaires are needed.
E a c h l u m i n a i r e m u s t b e p e r m a n e n t l y
connected to mains power supply. In normal
operation (L1 connected to L) the led strip
lights and the battery is charging. In case of
a mains power supply failure the luminaire will
light the led strip automatically in emergency
mode (powered by its battery). When the
mains power supply is restored the device
turns to normal operation.
OPERATION
Battery Charging
The battery charging is completely controlled.
In this case, the best possible
maintenance is achieved, as well as the
elongation of its duration. When the battery
has completely charged, it charges with a
maintenance current.
Battery Cut-off
The luminaire enters in this operation when
the mains power supply fails and battery has
lost its energy. During this operation the
luminaire enters the idle state and battery
consumption is negligible, in order to be
protected from deep discharge.
Page 1 from 4
GR-579/L/90/WP
EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3, EN 1838
Painted steel plate (RAL 7036), Bayblend FR3010, transparent polycarbonate
Congratulations for your selection to buy this product.
Olympia Electronics - European manufacturers.
High Quality European based Manufacturers
220-240V AC/50-60Hz
2x9W / 2x9.5VA - PF: 0.95/230V
2x4.8V/1.5Ah
From overcharge and deep discharge
Charge LED, Lamp Fault LED, Battery LED
90 min
White LEDs
2x680lm / 2x340lm
5 to 40 C
Up to 95%
740 x 400 x 185 mm
11550gr
3 years (1 year for the batteries)
Manual Test
This test can be done by placing the test card
on the side of the indications (page 4)
remove it instantly. An operation test is initiated
and the light source and the emergency circuit
of the device is monitored. The manual test can
be conducted only if the mains power supply
and the battery is connected. During this test
period all indication LEDs are OFF.
Automatic Operational Test
This test includes all the operations that provide
the manual test and is conducted automatically
every 15 days. In order to be performed, the
mains power supply and the battery should be
connected.
battery
Automatic Autonomous Test
The Automatic Autonomous Test is conducted
and measures the device's back up operation
and emergency duration. This test is conducted
automatically every 6 months. In order to be
performed, the mains power supply and the
battery should be connected and fully charged.
If the battery is not fully charged, the test is
postponed until the battery is completely
charged. If during this test, the autonomy is less
than nominal, then the battery fault led turned
on continuously and the battery must be
replaced.
GR-579/L/180/WP
2x4.8V/3Ah
24 h
180 min
IP 65
o
11730gr
923579000_09_003
and

Advertisement

loading

Summary of Contents for olympia electronics GR-579/L/90/WP

  • Page 1 TYPICAL WEIGHT 3 years (1 year for the batteries) GUARANTEE Congratulations for your selection to buy this product. Olympia Electronics - European manufacturers. GENERAL Manual Test These luminaires are used in places where This test can be done by placing the test card emergency luminaires are needed.
  • Page 2 Back Up Operation 2. The device must be connected to the The autonomous duration of battery during m a i n s p o w e r s u p p l y t h r o u g h a f u s e emergency mode is at least the one that is dependent on the total amount of the line’s stated...
  • Page 3 130m 64,5 cm 74 cm cable gland Photo 1 Photo 2 External switch Link Controlled maintained operation Permanent maintained operation TYPICAL SYMBOLS Exit routs Exit rout Emergency phone Except for typical symbols all luminaires can be constructed after request with any other symbols.
  • Page 4 Olympia Electronics reserves the right to repair or to replace the returned goods and to or not charge the buyer depending on the reason of defection. Olympia Electronics reserves the right to charge or not the buyer the transportation cost.

This manual is also suitable for:

Gr-579/l/180/wp