CommScope SYSTIMAX 360 Instructions Manual page 9

Ultra high-density shelf
Hide thumbs Also See for SYSTIMAX 360:
Table of Contents

Advertisement

www.commscope.com
Step 4 – Mount Modules/Panel in Shelf
Before installing modules/panels be sure any pre-installed cable sub-units are behind pivot mount panels and
provide enough clearance for panel installation.
Module/Panel Installation
1. Insert panel/module at an angle into one
side of side of the shelf so that pivot lock
pin engages in hole in pivot mounting
bracket. Be sure panel/module is oriented
with the trough opening facing up. Install
lowest panel first.
2. Pivot other side of panel/module down into
shelf so that the pivot lock pin is in back of
the pivot bracket.
Note: Panel/module pivot lock pin can only
be inserted from the rear of pivot mounting
bracket.
3. Depress the lever arm on the pivot
mounting
bracket
panel/module forward until pivot lock
pin engages the hole in pivot mounting
bracket.
4. Release lever arm of pivot mounting
bracket to secure the panel/module in
place.
Subsequent panels, up to three total in the
1U shelf, may be installed on top of the
base
module/panel
instructions above for each panel using
progressively higher pivot pin positions.
and
slide
following
the
Pivot
mounting
bracket
Pivot lock pin
Lever arm
860479229
Issue 7, May 2013
Trough in
"up" position
Pivot lock pin
to rear of mounting
bracket
Holes in
pivot mounting
bracket
Pivot lock
pin
Page 9 of 15