Method B
1. Working back from where cable enters shelf (at cable gland), carefully dress cable toward opposite side of
shelf. Route cable over slide rail, taking care to not exceed minimum bend radius.
2. From shelf slide, route cable to equipment rack and loosely secure cable to rack upright approximately
3 inches (76mm) above or below shelf, using a cable tie or hook-and-loop strip.
3. Verify that shelf retracts and extends fully before proceeding.
Method B
Slack loop in cables
with shelf in retracted position
4. The above figure shows typical fiber loop for both Method A and Method B fiber routing when shelf is
retracted.
Step 2B – Routing Multiple Cables into Sliding Shelf
Cabe entry port
Store loop in cables
with shelf in retracted position
1. Route cables, one at a time, into fully extended sliding shelf as outlined in Step 2A.
Shelf fully retracted
(Method A Shown)
Shelf fully retracted
Hook-and-loop strip
Issue 7, May 2013
Cable ties or
hook-and-loop strips
Method A
Cable ties or
hook-and-loop strips
860479229