Input Register - Siemens SIMATIC S7-1200 Manual

Controlling several fans (ebm-papst) via modbus rtu
Hide thumbs Also See for SIMATIC S7-1200:
Table of Contents

Advertisement

3 Mode of Operation
Address
Length
hex.
dec.
D150
53584
1
D151
53585
1
D152
53586
1
D153
53587
1
D15B
53595
1
D15C
53596
1
D15D
53597
1
D15E
53598
1
D1A0
53664
1
D1A1
53665
1
D1A2
53666
2
D1A4
53668
1
D1A5
53669
6
3.2.2

Input register

This application example allows you to read the following input registers through
the HMI:
Table 3-2
Address
hex.
D000
53248
D002
53250
D003
53251
D004
53252
D005
53253
D010
53264
D011
53265
D012
53266
D013
53267
D014
53268
D017
53271
D018
53272
D019
53273
D01A
53274
D01D
53277
D021
53281
D023
53283
D024
53284
Controlling several fans (ebm-papst) via Modbus RTU
Entry ID: 109476801,
V2.0,
Designation
Shedding function
Max. starting modulation level
Number of start attempts
Relay drop-out delay
Emergency operation running
direction
Emergency operation function on/off
Set value for emergency operation
Emergency operation time delay
Reference value of DC-link voltage
Reference value of DC-link current
Fan serial number
Fan production date
Fan type
dec.
Identification
Software name bus controller
Software version bus controller
Software name commutation controller
Software version commutation controller
Actual speed
Motor status
Warning
Link voltage
Link current
Electronics temperature
Current direction of rotation
Current modulation level
Current set value
Current parameter set
Current power
Sensor actual value 1
Sensor actual value 2
09/2018
Write
Reset
required
X
X
-
-
X
X
X
X
X
X
X
X
X
X
X
X
-
-
-
-
-
-
-
-
-
-
Designation
Password
required
X
-
X
-
X
X
X
X
-
-
-
-
-
12