Download Print this page

Siemens SICAM FCG Manual page 7

Advertisement

SICAM FCG Device
6MD2340
EMC Test for Noise Emission (Type Test)
Standard
Radio noise voltage to lines,
only auxiliary voltage
IEC-CISPR 11
Mechanical Stress Tests
Vibration and Shock Stress during Stationary Operation
Standards
Oscillation
IEC 62586-1, class II;
IEC 60068-2-6 test Fc
Shock
IEC 62586-1, class II;
IEC 60068-2-27 test Ea
Seismic vibration
IEC 62586-1, class II;
IEC 60068-3-3 test Fc
Vibration and Shock Stress during Transport
Standards
Oscillation
IEC 62586-1, class 2;
IEC 60068-2-6 test Fc
Shock
IEC 62586-1, class 1;
IEC 60068-2-27 test Ea
Shock
IEC 62586-1, class 1;
IEC 60068-2-29 test Eb
IEC/EN 61000-6-4
150 kHz to 30 MHz limit class A
IEC 62586-1 and IEC 60068
Sinusoidal
10 Hz to 60 Hz: ± 0.075 mm
amplitude; 60 Hz to 150 Hz:
1 g acceleration
Frequency sweep rate 1
octave/min 20 cycles in 3
orthogonal axes.
Semi-sinusoidal
5 g acceleration, duration 11 ms,
each 3 shocks in both directions
of the 3 axes
Sinusoidal
1 Hz to 8 Hz: ± 7.5 mm
amplitude (horizontal axis)
1 Hz to 8 Hz: ± 3.5 mm
amplitude (vertical axis)
8 Hz to 35 Hz: 2 g acceleration
(horizontal axis)
8 Hz to 35 Hz: 1 g acceleration
(vertical axis)
Frequency sweep 1 octave/min
1 cycle in 3 orthogonal axes
IEC 62586-1 and IEC 60068
Sinusoidal
5 Hz to 8 Hz: ± 7.5 mm
amplitude;
8 Hz to 150 Hz: 2 g acceleration
Frequency sweep 1 octave/min
20 cycles in 3 orthogonal axes
Semi-sinusoidal
15 g acceleration,
duration 11 ms,
Each 3 shocks (in both directions
of the 3 axes)
Semi-sinusoidal
10 g acceleration,
duration 16 ms,
Each 1000 shocks (in both
directions of the 3 axes)
Climatic Stress Tests
Temperatures
Standards
Type test (in acc. with IEC
60068-2-1 and IEC 60068-2-2,
Test bed for 16 h)
Permissible temporary
operating temperature (tested
for 96 h)
Recommended for permanent
operation (in acc. with IEC
60255-6)
Limit temperatures for storage
Limit temperatures for transport
Storage and transport with factory packaging
Humidity
Standards
Permissible humidity
Arrange the devices so that they are not exposed to direct sunlight or
extreme temperature changes. This will prevent condensation in the
device.
Dimensions
Mass
Dimension (W x H x D)
s
IEC 60068
-20 °C to +70 °C or -4 °F to +158 °F
-20 °C to +70 °C or -4 °F to +158 °F
-20 °C to +70 °C or +14 °F to +131 °F
-25 °C to +70 °C or -13 °F to +158 °F
-25 °C to +70 °C or -13 °F to +158 °F
IEC 62586-1 and IEC 60068
Mean value per year ≤ 75 % relative
humidity; on 10 days and 40 °C of the
year up to 93 % relative humidity;
condensation is not allowed.
approx. 0.550 kg
96 mm x 96 mm x 100 mm
3.78 in x 3.78 in x 3.94 in