CurrentWatch™ ECS7 Series Current Switches
Self-Calibrating AC Current Switches
with Solid State Outputs
Current Switch Operation
Model
Output Diagram
Underload Only Models
Overload Only Models
Over/Underload Models
Ranges and Maximum Amps
Maximum Amps
Housing
Range
Continuous
Solid Core
1.5-150 A
500 A
Split Core
2.8-150 A
500 A
Troubleshooting
Problem
Solution
Switch is
Switch may have been overloaded and contacts are burned out.
always
Check the output load, remembering to include inrush on inductive
tripped.
loads (coils, motors).
Switch will
For split core models, the core contact area may be dirty. Open the
not trip.
sensor and clean the contact area.
Switch may have been overloaded and contacts are burned out.
Check the output load, remembering to include inrush on inductive
loads (coils, motors).
Make sure function switch is in "RUN" mode.
Output Open
(LED Fast)
Calibration Point
Output Closed
(LED Slow)
Output Open
(LED Off)
(LED Slow)
Output Closed
115% of Calibration Point
Calibration Point
(LED Fast)
Output Open
(LED Off)
(LED Slow)
Output Open
115% of Calibration Point
Output Closed
(LED Fast)
85% ofCalibration Point
Output Open
(LED Slow)
(LED Off)
6 sec.
1 sec.
500 A
1,000 A
500 A
1,000 A
Instructions Publication P51922
Specifications
Specification
Value
Power Supply
Self Powered–No Power Supply Needed
Output
Magnetically Isolated Solid State Switch
Output Rating
Normally Open (N.O.) Models: 0.30 A @ 135 VAC/DC
Off-State Leakage
< 10 µA
Response Time
200 ms
Setpoint
Overload Only Models: +15% of Load
Underload Only Models: -15% of Load
Over/Underload Models: ±15% of Load (Operating
Window)
Setpoint Ranges
Solid Core: 1.5-150 A
Split Core: 2.8-150 A
Hysteresis
Approx. 5% of Setpoint
Isolation Voltage
UL Listed to 1,270 VAC, Tested to 5,000 VAC
Frequency Range
6-100 Hz
Sensing Aperture
Solid Core Models: 0.75 in. (19 mm) dia.
Split Core Models: 0.85 in. (21.7 mm) sq.
Housing
UL94 V0 Flammability Rated
Environmental
Operating Temperature: -4 to 122°F (-20 to +50°C)
Humidity: 0-95% RH, Non-Condensing
Approvals
UL Listed, E117028
UL tested to Canadian safety standards
CE
RoHs Compliant
Effective July 2017
EATON www.eaton.com
3

Advertisement

loading

This manual is also suitable for:

Currentwatch ecs701scCurrentwatch ecs700scCurrentwatch ecs702scCurrentwatch ecs711spCurrentwatch ecs710spCurrentwatch ecs712sp