ABB ACS880-07 User Manual page 50

Emergency stop, configurable stop category 0 or 1 (option +q979)
Hide thumbs Also See for ACS880-07:
Table of Contents

Advertisement

50 Start-up and validation test
Action
Make sure that you cannot start the drive or motor from any control location. Make sure that the drive
or motor does not start when you switch the start signal off and on, or push the start key of the panel
when the panel is in local control mode.
Switch off the drive start signal.
Turn the emergency stop button [S61] until it releases and returns to the up position.
Push the emergency stop reset button [S62]. Make sure that:
• the emergency stop reset button indicator light [S62] goes off.
• the drive does not restart automatically at this point.
Power up the drive:
• If the drive tripped on a fault, reset the faults from the drive
• Make sure that the operating switch is set to ON (1)
• Switch on the drive start signal.
For more information, see the hardware manual.
Restart the drive and make sure that the drive and the motor operate normally.
Do the test again from each operating location (for every emergency stop button and reset button).
Save the FSO safety file with the button Save safety file in the Drive composer pro PC tool.
Fill in and sign the validation test report. Store the report in the logbook of the machine.