■ Pipe insulation
• Apply pipe insulation separately to liquid, gas, and balance lines.
• All insulation should have a minimum temperature rating of 248°F (120°C).
■ Finishing pipe work
1. After all piping and insulation is complete. Fill the remaining gap at the piping panel with silicon sealer.
2. If the piping was routed down or to the side, the remaining gap should be filled with silicon sealer.
When not using the piping cover
Piping/wiring panel
Pipe routed to side
Fill space with silicon sealer
Pipe routed to front
Pipe routed down
8

Electric wiring

WARNING
The equipment shall be installed in compliance with NEC and local codes.
CAUTION
• Do not connect high voltage power wires to the control terminal blocks (U1, U2, U3, U4, U5, U6);
• All fi eld wiring insulation rating must comply with NEC and local codes.
• All wiring must be strained relieved as specifi ed by NEC and local codes.
• Refrigerant piping and control wiring should use the same routing.
• Do not energize the indoor units until leak check and vacuuming are completed.
• For indoor unit power and control wiring see indoor unit installation instructions.
NOTE
• Use copper supply wires.
• Use UL wires rated 600V for the system interconnection wires.
• Use UL wires rated 300V for remote control wires.
29-EN
– 15 –
■ Power supply specifi cations
Every outdoor unit must have a dedicated power supply.
◆ Power wiring selection
Power Supply
Model name
Nominal
(Standard Model)
Voltage
MMY-MAP0726HT6P-UL
460 V
MMY-MAP0966HT6P-UL
460 V
MMY-MAP1206HT6P-UL
460 V
MMY-MAP1446HT6P-UL
460 V
MMY-MAP1686HT6P-UL
460 V
MMY-AP1926HT6P-UL
460 V
MMY-AP2166HT6P-UL
460 V
MMY-AP2406HT6P-UL
460 V
MMY-AP2646HT6P-UL
460 V
MMY-AP2886HT6P-UL
460 V
MMY-AP3126HT6P-UL
460 V
MMY-AP3366HT6P-UL
460 V
MMY-AP3606HT6P-UL
460 V
MMY-AP3846HT6P-UL
460 V
MMY-AP4086HT6P-UL
460 V
MMY-AP4326HT6P-UL
460 V
MMY-AP4566HT6P-UL
460 V
Power Supply
Model name
Nominal
(Space Saving Model)
Voltage
MMY-AP192S6HT6P-UL
460 V
MMY-AP240S6HT6P-UL
460 V
MMY-AP288S6HT6P-UL
460 V
MMY-AP408S6HT6P-UL
460 V
NOTE
Be sure to follow the above specifications when plugging in.
L
L
L
L
1
2
3
Main power circuit
Disconnect per NEC
breaker
and local codes.
MCA: Minimum Circuit Amps
MOCP: Maximum Overcurrent Protection (Amps)
Voltage Range
MCA
Phase and
Min.
Max.
(A)
frequency
(V)
(V)
3 ~ 60 Hz
414
506
12.9
3 ~ 60 Hz
414
506
20
3 ~ 60 Hz
414
506
23
3 ~ 60 Hz
414
506
25
3 ~ 60 Hz
414
506
31
3 ~ 60 Hz
414
506
20 + 20
3 ~ 60 Hz
414
506
23 + 20
3 ~ 60 Hz
414
506
25 + 20
3 ~ 60 Hz
414
506
25 + 23
3 ~ 60 Hz
414
506
25 + 25
3 ~ 60 Hz
414
506
31 + 25
3 ~ 60 Hz
414
506
31 + 31
3 ~ 60 Hz
414
506
23 + 23 + 23
3 ~ 60 Hz
414
506
25 + 23 + 23
3 ~ 60 Hz
414
506
25 + 25 + 23
3 ~ 60 Hz
414
506
31 + 25 + 23
3 ~ 60 Hz
414
506
31 + 31 + 23
Voltage Range
MCA
Phase and
Min.
Max.
(A)
frequency
(V)
(V)
3 ~ 60 Hz
414
506
23 + 12.9
3 ~ 60 Hz
414
506
23 + 23
3 ~ 60 Hz
414
506
31 + 23
3 ~ 60 Hz
414
506
31 + 23 + 23
L
L
L
L
L
1
2
3
1
2
3
MOCP
(A)
20
25
30
35
40
25 + 25
30 + 25
35 + 25
35 + 30
35 + 35
40 + 35
40 + 40
30 + 30 + 30
35 + 30 + 30
35 + 35 + 30
40 + 35 + 30
40 + 40 + 30
MOCP
(A)
30 + 20
30 + 30
40 + 30
40 + 30 + 30
30-EN