Summary of Contents for Tekmar Universal Reset Module 422
Page 1
Introduction The following wiring brochure describes how to wire the tekmar Universal Reset Module 422. The 422 is to be installed in an enclosure together with a tekmar Zone Manager. The 422 controls one boiler (on-off or modulating), DHW, setpoint and one mixing (either variable speed injection or floating action).
Page 2
Table of Contents Wiring Symbols & Definitions ........2 Troubleshooting Instructions ........9-11 Module Installation ............3 Technical Data .............. 12 Electrical Drawings ............4-7 Wiring Specification Guide ........... 12 Wiring the Control ............8-9 Wiring Symbols Demand, signals control to operate. Requires a power and neutral connection. Use 24 Fuse, field replaceable.
Page 3
Module Installation Install the Universal Reset Module 422 in the left side of a tekmarNet ® 4 (tN4) wiring enclosure. The enclosure comes with a Zone Manager pre-installed in the right side. Review the figure below to understand the installation of the 422: To Install the 422 1.
Page 4
24 V (ac) 8 VA 51 52 53 54 55 63 64 Output 1 VA Powered Output Do not apply power Universal Reset Module 422 Menu Item Connections tN4 Boiler / Mix 2 tektra 991-03 Boil Sens Sup / Ret...
Page 5
24 V (ac) 8 VA 51 52 53 54 55 63 64 Output 1 VA Powered Output Do not apply power Universal Reset Module 422 Menu Item Connections tN4 Boiler / Mix 2 tektra 991-03 from Zone Boil Sens Sup / Ret D 422 Boiler On-Off...
Page 6
24 V (ac) 8 VA 51 52 53 54 55 63 64 Output 1 VA Powered Output Do not apply power Universal Reset Module 422 Menu Item Connections tN4 Boiler / Mix 2 tektra 991-03 from Zone Boil Sens Sup / Ret D 422 Boiler On-Off...
Page 7
24 V (ac) 8 VA 51 52 53 54 55 63 64 Output 1 VA Powered Output Do not apply power Universal Reset Module 422 Menu Item Connections tN4 Boiler / Mix 2 tektra 991-03 from Zone Boil Sens Sup / Ret D 422 Boiler On-Off...
Page 8
The following section explains how to wire individual terminals. devices to the Universal Reset Module 422. For step by • • Refer to the current and voltage ratings at the back step wiring refer to the terminal number on the right of of this brochure before connecting devices to this the page.
Page 9
Note: Some modulating boilers may also require an on / • • The control provides a 0-10 V (dc) modulating output to a single modulating boiler or to a tekmar boiler staging off signal in addition to the modulating signal. See terminals control that accepts an External Input Signal in place 51 and 52.
Page 10
Troubleshooting the Wiring General The following tests are to be performed using standard Test Meter testing practices and procedures and should only be carried Control Terminals out by properly trained and experienced persons. A good quality electrical test meter, capable of reading from at least 0-300 V (ac), 0-30 V (dc), 0-2,000,000 Ohms, and testing for continuity is essential to properly test the wiring and sensors.
Page 11
Mod (dc) terminals (64-65). The reading should vary between 0 V (dc) and 10 V (dc). Testing tekmar Sensors Terminals 66-70 To test the sensors, the actual temperature at each sensor • • Disconnect each sensor from the control.
Need help?
Do you have a question about the Universal Reset Module 422 and is the answer not in the manual?
Questions and answers