Daikin DBG Series Service Instructions Manual page 3

Gas electric/cooling commercial package units with r-410a refrigerant 15 - 25 tons & accessories
Table of Contents

Advertisement

SAFE REFRIGERANT HANDLING
While these items will not cover every conceivable situation, they should serve as a useful guide.
WARNING
Refrigerants are heavier than air. They can "push out"
the oxygen in your lungs or in any enclosed space.To
avoid possible difficulty in breathing or death:
• Never purge refrigerant into an enclosed room or
space. By law, all refrigerants must be reclaimed.
• If an indoor leak is suspected, thoroughly ventilate
the area before beginning work.
• Liquid refrigerant can be very cold. To avoid possible
frostbite or blindness, avoid contact with refrigerant
and wear gloves and goggles. If liquid refrigerant
does contact your skin or eyes, seek medical help
immediately.
• Always follow EPA regulations. Never burn refrig-
erant, as poisonous gas will be produced.
WARNING
To avoid possible injury, explosion or death, practice
safe handling of refrigerants.
The compressor POE oil for R-410A units is
extremely susceptible to moisture absorption and
could cause compressor failure. Do not leave system
open to atmosphere any longer than necessary
for installation.
WARNING
System contaminants, improper service procedure
and/or physical abuse affecting hermetic compressor
electrical terminals may cause dangerous system
venting.
The successful development of hermetically sealed refriger-
ation compressors has completely sealed the compressor's
moving parts and electric motor inside a common housing,
minimizing refrigerant leaks and the hazards sometimes
associated with moving belts, pulleys or couplings.
Fundamental to the design of hermetic compressors is
a method whereby electrical current is transmitted to the
compressor motor through terminal conductors which pass
through the compressor housing wall. These terminals are
sealed in a dielectric material which insulates them from
the housing and maintains the pressure tight integrity of
the hermetic compressor. The terminals and their dielectric
embedment are strongly constructed, but are vulnerable to
careless compressor installation or maintenance procedures
and equally vulnerable to internal electrical short circuits
caused by excessive system contaminants.
To avoid possible explosion, use only returnable (not
disposable) service cylinders when removing refrig-
erant from a system.
• Ensure the cylinder is free of damage which could
lead to a leak or explosion.
• Ensure the hydrostatic test date does not exceed
5 years.
• Ensure the pressure rating meets or exceeds 400
lbs.
When in doubt, do not use cylinder.
In either of these instances, an electrical short between the
terminal and the compressor housing may result in the loss of
integrity between the terminal and its dielectric embedment.
This loss may cause the terminals to be expelled, thereby
venting the vaporous and liquid contents of the compressor
housing and system.
A venting compressor terminal normally presents no danger
to anyone, providing the terminal protective cover is properly
in place.
If, however, the terminal protective cover is not properly in
place, a venting terminal may discharge a combination of
(a) hot lubricating oil and refrigerant
(b) flammable mixture (if system is contaminated
with air)
in a stream of spray which may be dangerous to anyone in
the vicinity. Death or serious bodily injury could occur.
Under no circumstances is a hermetic compressor to be elec-
trically energized and/or operated without having the terminal
protective cover properly in place.
See Service Section S-17 for proper servicing.
3