Daikin DBG Series Service Instructions Manual page 106

Gas electric/cooling commercial package units with r-410a refrigerant 15 - 25 tons & accessories
Table of Contents

Advertisement

UNIT WIRING DIAGRAMS
LINE VOLTAGE
L1
6
L1
BK
BK
BK
NOTES:
1. REPLACEMENT WIRE MUST BE SAME SIZE AND TYPE OF INSULATION AS ORIGINAL (USE COPPER CONDUCTORS ONLY).
2. THE CONTROL TRANSFORMER HAS MULTIPLE HIGH VOLTAGE TAPS.
ENSURE WIRE CONNECTIONS ARE CORRECT FOR UNIT SUPPLY VOLTAGE RATING
3. SEE CONTROL DIAGRAM FOR CONTROL TRANSFORMER LOW VOLTAGE CONNECTIONS
4. OPTIONAL; CB1,CB2,BC2 AND ASSOCIATED WIRING IS PRESENT ONLY WITH 2-SPEED EVAPORATOR MOTOR.
5. USE COPPER CONDUCTORS ONLY. UNIT TERMINALS ARE NOT DESIGNED FOR OTHER CONDUCTORS.
THE USE OF OTHER TYPE CONDUCTORS MAY CAUSE DAMAGE TO THE UNIT.
6. SEE ACCESSO RY KIT LITERATURE FOR OPTIONAL CONVENIE NCE OUTLET WIRING DIAGRAM.
7. IF LOW AMBIENT KIT INSTALLED, DISCONNECT CONDENSER MOTOR WIRES (BK,BR,YL) FROM CMC1 (T1,T2,T3)
AND CONNECT TO CORRESPO NDING BK,BR,YL WIRES ON LOW AMBIENT HARNESS (INSULATED MALE QUICK CONNECT).
ALSO CONNECT LOW AMBIENT HARNESS WIRES (BK,BR,YL) (INSULATED FEMALE QUICK CONNECT) TO T1,T2,T3 ON CMC1.
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
106
L2
L3
GND
L2
L3
PB
RD
YL
BR
PU
OR
CC1
BK
BK
L1
T1
BK
RD
RD
L2
T2
RD
YL
YL
YL
L3
T3
CC2
BK
BK
L1
T1
BK
RD
RD
L2
T2
RD
PU
PU
L3
T3
PU
FB 1
BK
BK
F1
BR
BR
BR
F2
PU
PU
PU
F3
3
460V
OR
TR2
COM
575V
230V
TR1
2
BK
RD
OR
BK
BK
VMR
IIC
RD
1
3
IGN
OR
IGN
FB 2
BK
BK
BK
L1
F4
RD
RD
RD
RD
L2
F5
OR
OR
OR
L3
F6
BK
L1
L2
RD
OR
L3
DBG300XXX(4,7)(B,V)****AB
POWER DIAGRAM
DCG300***(4,7)
BK
BK
L1
L2
COMP 1
GY
L3
BK
L1
COMP 2
L2
L3
BK
BK
BR
PU
BR
PU
BK
BK
BK
BR
24V CNTL
RD
PU
VOLTAGE
PU
PU
LINE
VOLTAG E
BK
OR
RD
RD
BK
WH
WH
GR
VM
BK
BK
4
CB1
HIGH
BC1
SPEED
YL (11)
BK
BK
T1
L1
T1
T2
RD
L2
RD
YL (13)
T2
OR
YL (12)
T3
OR
L3
T3
CB2
LOW
BC 2
SPEED
BK (1)
T1
YL
YL
L1
T1
T2
BL
L2
BL
BK (3)
T2
T3
GY
BK (2)
GY
L3
T3
IIC DIAGNOSTIC BLINK CODES
STATUS LIGHT
EQUIPMENT STATUS
CHECK
ON
NORMAL OPERATION
-------
CHECK INPUT POWER
NO POWER OR
OFF
CHECK FUSE ON CONTROL
INTERNAL CONTROL
REPLACE CONTROL
GAS FLOW
GAS PRESSURE
GAS VALVE
IGNITION FAILURE
1 BLINK
OPEN ROLLOU T SWITCH
FLAME SENSER
OPEN AUX LIMIT SWITCH
FLAME ROLLO UT
BAD SWITCH
AUX.LIMIT OPEN
CHECK PRESSURE
2 BLINKS
PRESSURE SWITCH OPEN
SWITCH
PRESSURE SWITCH CLOSED
CHECK PRESSURE
3 BLINKS
WITHOUT INDUC ER ON
SWITCH
MAIN LIMIT OPEN
4 BLINKS
OPEN LIMIT SWITCH
BAD SWITCH
5 BLINKS
FALSE FLAME SENSED
STICKING GAS VA LVE
3 MIN. COMP.
COMPRESSOR OUTPUT
6 BLINKS
ANTI-CYCLE TIMER
DELAY
CCAS1
BK
GY
CCH1
GY
BK
GR
CCAS2
BR
BK
CCH2
PU
BK
GR
CMC 1
P
L
F
P
L
M
L1
T1
BK
BK
BK
1
1
L1
L2
T2
BR
BR
BR
CM1
2
2
L2
YL
L3
T3
YL
PU
3
3
L3
T3 T2 T1
7
LAC MC
BK
L1
T1
BK
L2
T2
BR
BR
L3
T3
YL
YL
CMC 2
PLM
PLF
T1
BK
BK
BK
L1
1
1
L1
L2
BR
BR
T2
BR
2
2
L2
CM2
L3
T3
PU
PU
PU
3
L3
3
COMPONENT LEGEND
BLOWER CONTACTOR
BC
BLOWER RELAY
BR
CIRCUIT BREAKER
CB
COMPRESSOR CONTACTOR
CC
CC AUX SWITCH
CCAS
CCH
CRANK CASE HEATER
CCR
COMPRESSOR CONTACTOR RELAY
COMPRESSOR
COMP
CM
CONDENSER MOTOR
CMC
CONDENSER MOTOR CONTACTOR
CMR
CONDENSER MOTOR RELAY
ECONOMIZER
ECON
EVAPORATOR MOTOR
EM
CM/CCH/TR1 FUSE BLOCK
FB1
FB2
EM FUSE BLOCK
FM
EVAPORATOR FREEZE STAT
MODULE
F1, F2, F3
CM/CCH/TR1 FUSES
F4, F5, F6
EM FUSES
HIGH PRESSURE SWITCH
HPS
LACMC
LOW AMBIENT CONDENSER MOTOR
CONTACTOR
LOW AMBIENT MODULE
LAM
LOW AMBIENT RELAY
LAR
LOW AMBIENT TIMER
LAT
LOW PRESSURE SWITCH
LPS
POWER DISTRIBUTION BLOCK
PB
FEMALE PLUG / CONNECTOR
PLF
PLM
MALE PLUG / CONNECTOR
TB1
LOW VOLTAGE TERMINAL BLOCK 1
LOW VOLTAGE TERMINAL BLOCK 3
TB3
CONTROL TRANSFORMER
TR1
(LINE VOLTAGE/24VAC)
FACTORY WIRING
LINE VOLTAGE
GR
EM
LOW VOLTAGE
O PTIONAL
HIGHVOLTAGE
FIELD WIRING
HIGHVOLTAGE
LOW VOLTA GE
WIRE CODE
BK
BLACK
BL
BLUE
BR
BROWN
GR
GREEN
GY
GRAY
OR
ORANGE
PK
PINK
PU
PURPLE
RD
RED
WH
WHITE
YL
YELLOW