Download Print this page

Honeywell T775L Series Installation Instructions Manual page 20

Electronic stand-alone staging controller

Advertisement

T775L SERIES 2000 ELECTRONIC STAND-ALONE STAGING CONTROLLER
SETUP
OUTPUTS
LOOP 1
RESET
Fig. 44. Setup - Outputs - Loop 1 - Reset.
SETUP
OUTPUTS
LOOP 1
Fig. 45. Setup - Outputs - Loop 1 - Exit.
SETUP
OUTPUTS
RELAY 9
Fig. 46. Setup - Outputs - Relay Menu.
62-0257—11
SETUP
OUTPUTS
LOOP 1
RESET
YES-BOILER
YES-OTHER
NO
USE
RESET
FOR
LOOP 1
M24452
SETUP
OUTPUTS
LOOP 1
# RELAYS
INTEGRAL
DERIVATIVE
ON DELAY
OFF DELAY
SCHEDULE
RESET
EXIT
M24453
SETUP
OUTPUTS
RELAY 9
SCHEDULE
RESET
RESET RT
EXIT
M24454
1.3.4.7. RESET
(Loop Reset)
This selection enables the controller's Reset function, and
allows each output to be individually programmed for
Reset or No Reset.
IMPORTANT
To use the Reset function of the controller, the
first loop must be set for Reset.
The RESET choice is offered for all outputs in setup
mode, and you can set any or all of them for Reset=YES
or Reset=NO. The default is Reset=NO.
For the remaining outputs, if Reset=YES, then these
outputs use the reset curve programmed for the first
output.
1. From the Loop 1 menu, use the and  buttons to
highlight RESET.
2. Press the  button to display the value.
Default: NO
3. Use the  and  buttons to select the value.
4. Press the  button to accept the value and display
the Loop 1 menu.
• If you select YES, then the second loop (and any
additional relays) display this Setup option.
• If you select NO, then No Reset is configured.
1.3.4.8. Exit Loop Setup
Use the  and  buttons to highlight EXIT and press the
 button.
If you have additional relay outputs, continue with "1.3.5.
Setting up the Relays". Otherwise, go to "1.4. Exiting
Setup" on page 22
1.3.5. Setting up the Relays
1. From the Outputs menu, use the  and  buttons
to highlight the desired relay.
2. Press the  button to display the selected relay
menu.
NOTE: There can be up to two additional relays.
For example: If there are 12 total relays, and
Loop 1 uses relays 1–4, and Loop 2 uses relays
5–8, the two available additional relays will be 9
and 10. (In this example, relays 11 and 12 are
not usable since there can be only two additional
relays.)
Continue with the remainder of this section to setup the
relay outputs.
20