SETUP
OUTPUTS
# LOOPS
Fig. 29. Setup - Sensors - Number of Sensors.
SETUP
OUTPUTS
OPTIONS
Fig. 30. Setup - Outputs - Options Menu.
SETUP
OUTPUTS
OPTIONS
USE SCHED
Fig. 31. Setup - Outputs - Options - Schedule.
T775L SERIES 2000 ELECTRONIC STAND-ALONE STAGING CONTROLLER
SETUP
OUTPUTS
# LOOPS
2
ENTER
NUMBER OF
LOOPS
M24438
SETUP
OUTPUTS
OPTIONS
USE SCHED
MIN OFF
MIN ON
DI OPTS
SHOW RT
SYNC
EXIT
M24520A
SETUP
OUTPUTS
OPTIONS
USE SCHED
YES
NO
USE
SCHEDULE
FOR
OUTPUTS
M24440
1.3.2. Number of LOOPS
The value entered here determines the number of loops
displayed on the home screen.
1. From the Outputs menu, highlight # LOOPS then
press the  button to display the number of loops.
2. Use the  and  buttons to enter the number of
loops (1 or 2).
Default: 1
3. Press the  button to accept the value and display
the Outputs menu.
1.3.3. OPTIONS
1. From the Outputs menu, use the and  buttons
to highlight OPTIONS.
2. Press the  button to display the Options menu.
1.3.3.1. USE SCHED
1. Press the  button to display the schedule selec-
tions.
2. Use the and  buttons to highlight YES or NO.
Default: NO
3. Press the  button to accept the value and display
the MIN OFF option.
Selecting NO disables scheduling for all outputs.
Selecting YES enables scheduling for the setpoint.
However, each individual output can be removed from
scheduling as desired.
With Scheduling enabled, when you return to Program
mode, the new option for Scheduling displays. You can
press the HOME button and then the MENU button to
view the Schedule options in the menu.
15
62-0257—11

Advertisement

loading

This manual is also suitable for:

2000 seriesT775l2007