Table 3. Display indications and meanings
Indication
Meaning
(after 2 s)
Input internal control
in % (S-02 = int)
Input internal control
in flow rate (S-02 = int)
Voltage control signal
Voltage control signal
Current control signal
Current control signal
ON / OFF
Floating input
Remote control
PWM 5 sec
PWM 25 sec
Internal input
Flow rate on
Min. flow rate selection
display
(default: 0)
Flow rate on
Max. flow rate selection
display
(default: model-dependent)
V5004TF ACTUATOR – INSTALLATION INSTRUCTIONS
Description
Select type of input internal control using UP / DOWN buttons and
then press MODE button to confirm.
Control with voltage signal
Control with voltage signal
Control with current signal
Control with current signal
24 V: open. 0 V: close
24 V open if white wire (3) connected;
24 V close if green wire (4) connected
Not available
PWM (0.1...5 sec)
PWM (0.1...25 sec)
Flow rate set by onboard display and buttons. Push MODE button,
wait until "SET" is replaced by flow rate indication (or flow rate %,
depending upon S-01), set the flow rate using the UP / DOWN
buttons, and then press the MODE button to confirm.
Set min. flow rate using the UP / DOWN buttons and then press
the MODE button to confirm.
Set max. flow rate using the UP / DOWN buttons and then press
the MODE button to confirm.
5
MU1B-0655GE51 R1019A