KFCC Field Connection Checklist

Power to KFCC Cabinet and Lights
115 VAC power for controls (terminals H1, N1)
115 VAC power for hood lights, one per light circuit
(terminals H2, N2 | H3, N3 | H4, N4)
Connect lights, one per light circuit
(terminals B2, W2 | B3, W3 | B4, W4)
(Lights may be directly wired to switch)
Power for Fans
115/200/208/230/277 VAC power, single phase fans
from breaker (terminals L1, L2)
208/230/277/460/575 VAC power, three phase fans
from breaker (terminals L1, L2, L3)
115 VAC power for single phase to fan (contactor/
overload T3, terminal L2 is neutral)
208/230/277/460 VAC power to single phase fan
(contactor/overload T1, T3)
208/460/575 VAC power to three phase fan
(contactor/overload T1, T2, T3)
Fire System
Microswitch C, N .O ., and N .C . (terminals C1, NO1,
NC1)
Spare Fire Contacts
Spare, dry relay contact (terminals C3, NO3, NC3)
Spare, dry relay contact (terminals C4, NO4, NC4)
Switches - if equipped
Fan, 1-Speed (terminals S_H, S_; S_N is neutral if
lighted)
Fan, 2-Speed (terminals S_F, S_S, S_)
Light (terminals H2, B2 or H3, B3 or H4, B4; may be
directly wired to hood lights)
Thermal, heat only (terminals R, W1)
Thermal, cool only (terminals R, Y1)
Thermal, heat and cool (terminals R, W1, Y1)
16
Kitchen Fan Control Center
MUA Interface - if equipped
To MUA Control Center (terminals R, G)
Power for Shunt Trip - if equipped
Shunt trip breaker coil (terminals STH, STN)
Additional Fire Contacts - if equipped
Spare, dry relay contact (terminals C9, NO9, NC9)
Spare, dry relay contact (terminals C10, NO10, NC10)
Additional Exhaust Contacts - if equipped
Spare, dry relay contact (terminals C7, NO7, NC7)
Spare, dry relay contact (terminals C8, NO8, NC8)
Additional Supply Contacts - if equipped
Spare, dry relay contact (terminals C5, NO5, NC5)
Spare, dry relay contact (terminals C6, NO6, NC6)
Exhaust Fan Failure Indicator - if equipped
Field provided airflow switch or current sensor
(terminals AF1, AF2)
Supply Fan Failure Indicator - if equipped
Field provided airflow switch or current sensor
(terminals AF3, AF4)
Status Lights (115 VAC) - if equipped
Status light one (terminals SL1, SL2)
Status light two (terminals SL3, SL4)
Digital Style Temperature Interlock - if equipped
Sensor(s) (terminals T_-A, T_-B)
Thermostat Style Temperature Interlock - if equipped
Thermostat(s) (wired in parallel between terminals
T1-A, T1-B)
®