Digital Style Temperature Interlock Configuration
NOTE
This section only applicable if the KFCC is configured
with digital temperature interlock option .
Pre-programmed, digital temperature controller(s) will be
provided to monitor temperatures detected by sensor(s)
and engage fan(s) .
The fan(s) will start running when a temperature
exceeds the set point (defaulted at 90°F) plus differential
(defaulted at 10°F) . Once the temperature drops back
below the set point AND the fan(s) have been running
for a minimum run time (defaulted at 5 minutes), the
fan(s) will shut off .
OUTPUT
DIRECT OUTPUT 1
ON
OFF
DIFFERENTIAL
(DEFAULT = 10°F)
SET POINT
(DEFAULT = 90°F)
®
Calibration
Each controller is capable of monitoring up to three
individual sensors . There will be an individual set point
for each sensor input . The temperature set point may
need to be adjusted slightly depending on both ambient
and cooking conditions . To adjust the set points on the
OUT1
OUT2
°C
OUT1
OUT2
°C
controller, follow these instructions:
°F
°F
1 . Press
Set
OUT1
OUT2
°C
2 . Press
A
°F
OUT1
OUT2
A
U
°C
U
X
OUT1
OUT2
X
°C
°F
you wish to adjust (St1, St2, or St3) .
°F
Set
Set
3 . Press
Set
OUT1
OUT2
°C
A
U
X
°F
or
A
U
X
A
OUT1
OUT2
U
°C
X
value .
°F
4 . Press
A
Set
U
X
menu or wait 1 minute .
A
U
X
OUT1
OUT2
°C
Show Sensor Values
°F
OUT1
OUT2
°C
Press
Set
°F
value, and press these two buttons together again to
A
Set
U
X
see additional sensors connected . "Sd1" represents
A
U
X
sensor input one, "Sd2"represents sensor input two,
and "Sd3" represents sensor input three (respective to
each controller) . After 1 minute of no button presses, the
TEMPERATURE
controller will go back to displaying the first
programmed input (see parameters P31, P32, P33) .
button . 'St1" will appear .
Set
Set
Set
or
button to navigate to set point that
Set
OUT1
OUT2
°C
OUT1
Set
°F
button to view current set point . Press
Set
button to adjust and press
Set
Set
Set
A
U
X
+
buttons together to exit set point
Set
+
buttons together to show sensor and
Set
Set
Kitchen Fan Control Center
OUT2
°C
°F
button to store
Set
Set
Set
A
U
X
13