Lights Out In Fire; Additional Fire Contacts; Additional Exhaust Contacts - Greenheck KFCC Installation, Operation And Maintenance Manual

Kitchen fan control center
Table of Contents

Advertisement

Lights Out In Fire (Optional)
This option will turn off the kitchen hood lights in
Audible Alarm (Optional)
the event of a fire without the use of a shunt trip
breaker . If provided, this option will be factory wired .
Normal light circuit wiring should be followed . Please
NONE
see either Switches (Optional), Lights on page 8
or Combination Light/Fan Switch on page 9 for
additional wiring information .
Power for Shunt Trip (Optional)
For lights out in fire option, light circuit must not
exceed 900W maximum .
STH
STB1
STB2
Additional Fire Contacts (Optional)
The KFCC can include additional fire relays for shunt
MUA Interface (Optional)
trips, alarms, or additional utilities that need control
signals to be sent in the event of a kitchen fire . The
additional relay's state will only be changed if the
CONNECTIONS TO
R
dedicated fire system is wired into the KFCC . Wiring
TEMPERED MUA FAN
from additional relays to terminals will be done at the
TYP. THRU ALL
R
factory .
EXHAUST STARTERS
13 14
Additional Fire Relay
BL
13 14
• Power to terminal C9
• From terminal NO9 (normally open; closes in fire) to
device
Lights out in Fire (Optional)
• From terminal NC9 (normally closed; opens in fire)
to device
NONE
• Power to terminal C10
• From terminal NO10 (normally open; closes in fire)
to device
• From terminal NC10 (normally closed; opens in fire)
to device
RD
C9
BK
A
NO9
BR
NC9
B
RD
C10
BK
A
NO10
BR
NC10
B
Relay contacts will be dry . Power will need to be
provided to the common terminal on each set .
Contacts on and off with exhaust fan
Do not use additional relay contacts for power
RD
interruption to appliances . Contacts are rated up to
C7
BK
250 VAC and 8 amps maximum .
A
NO7
BR
Relay contacts will also switch state in the event
B
NC7
RD
power is lost to the control panel (terminals H1 and
C8
BK
N1) .
A
NO8
BR
B
NC8
10
Kitchen Fan Control Center
RD
C5
NOTE
STN
G
G
R12
BL
11 14
12
R5
11
14
22 21
R5
24
NOTE
14
R4
11
12
24
R4
21
22
Lights out in Fire (Optional)
Additional Exhaust Contacts (Optional)
Additional Fire Contacts (Optional)
The KFCC can include additional relays for devices that
activate when the exhaust fan is running . Wiring from
additional relays to terminals will be done at the factory .
Additional Exhaust Relay
A
• Power to terminal C7
• From terminal NO7 (normally open; closes with
B
exhaust) to device
• From terminal NC7 (normally closed; opens with
A
exhaust) to device
B
• Power to terminal C8
• From terminal NO8 (normally open; closes with
Additional Exhaust Contacts (Optional)
exhaust) to device
• From terminal NC8 (normally closed; opens with
exhaust) to device
Contacts on and off with exhaust fan
A
NO7
B
NC7
A
NO8
B
NC8
Extra Relay with Supply (Optional)
Relay contacts will be dry . Power will need to be
provided to the common terminal on each set .
Contacts are rated up to 250 VAC and 8 amps
maximum .
A
NO5
B
NC5
A
NO6
B
NC6
Supply Fan Failure Indicator (Optional)
SUPPLY AIR FLOW SWITCH FIELD WIRED
PR
AF3
Exhaust Fan Failure Indicator (Optional)
EXHAUST AIR FLOW SWITCH FIELD WIRED
PR
AF1
WWCP Interface
NONE
RD
C9
BK
NO9
12
R5
11
BR
NC9
14
RD
C10
BK
NO10
22 21
R5
BR
NC10
24
RD
C7
BK
14
R4
BR
11
12
RD
C8
BK
24
R4
BR
21
22
NOTE
RD
C5
BK
14
R3
11
BR
12
RD
C6
BK
24
R3
BR
21
22
AF2
LT3
WH
AF4
G
SF Failure Light
AF1
LT2
WH
AF2
G
EF Failure Light
NONE
®