Gas Piping Requirements

Gas Pressure Requirements
Inlet gas pressure must be maintained at 7.0" wc for Natural
Gas and 11.0" wc for Propane. Maximum inlet pressure must
not exceed 13.0" wc to prevent damage to the gas valve.
Gas piping must be sized and routed to provide the minimum
required pressure when the burner is operating at maximum
input. Consult your local utility on any questions on gas
pressure available, allowable pipe pressure drops, and local
piping requirements.
Table
16,
for sizing reference.
Table 18: Natural Gas Pipe Flow Capacity* (CFH)
Pipe Length
½
(ft)
10
132
20
92
30
73
40
63
50
56
60
50
70
46
80
53
90
40
100
38
125
34
150
31
175
28
200
26
*Assuming Pressure Drop of 0.3" Wc & Specific Gravity of 0.60
Table 19: Conversion for Specific Gravities other than 0.60
Natural Gas
0.50
0.60
0.70
0.80
0.90
1.00
Propane-Air
1.10
Propane
1.55
Butane
2.00
IM 1287 • REBEL APPLIED ROOFTOP
Table
17, and
Table 18
provided
Gas Capacity in CFH
Pipe Size-inches (Ips)
¾
1
278
520
1050
190
350
730
152
285
590
130
245
500
115
215
440
105
195
400
96
180
370
90
170
350
84
160
320
79
150
305
72
130
275
64
120
250
59
110
225
55
100
210
Multiplier
1.100
1.000
0.936
0.867
0.816
0.775
Multiplier
0.740
Multiplier
0.622
Multiplier
0.547
Install all piping in accordance with the National Fuel Gas Code
(ANSI Z223 .1), (NFPA 54-1999) and any applicable local codes.
Remove all burrs and obstructions from pipe. A drip leg must
be installed in the vertical line before each burner such that it
will not freeze. All pipe threads must have a pipe dope which is
resistant to the action of LP gas .
After installation, pressurize the piping as required and test
all joints for tightness with a rich soap solution or UL 913
combustible gas leak detector. Any bubbling is considered a
leak and must be eliminated.
2
1600
2050
1100
2100
890
1650
760
1450
670
1270
610
1150
560
1050
530
990
490
930
460
870
410
780
380
710
350
650
320
610
Table 20: Conversion for Pressure Drop other than 0.3"
Inches W .C .
Multiplier
Pressure Drop
0.1
0.577
0.2
0.815
0.3
1.000
0.4
1.16
0.6
1.42
0.8
1.64
88
Unit Maintenance
3
4800
8500
17500
3300
5900
12000
2700
4700
9700
2300
4100
8300
2000
3600
7400
1850
3250
6800
1700
3000
6200
1600
2800
5800
1500
2600
5400
1400
2500
5100
1250
2200
4500
1130
2000
4100
1050
1850
3800
980
1700
3500
Inches W .C .
Multiplier
Pressure Drop
1.0
1.83
2.0
2.58
3.0
3.16
4.0
3.65
6.0
4.47
8.0
5.15
www.DaikinApplied.com