Keypad And Display Menu Structure - Daikin Rebel Applied DPSA Installation And Start-Up Manual

Packaged rooftop heating and cooling 30 to 52 tons r-410a refrigerant
Hide thumbs Also See for Rebel Applied DPSA:
Table of Contents

Advertisement

Keypad and Display Menu Structure

Figure 61: Main Menu – Keypad/Display Menu Structure
The following is a description of the MicroTech 4 menu structure. These menus and items can all be displayed with the keypad/
display. Menu items displayed will change based on the selected unit configuration. Refer to
Figure 60: Main Menu – Keypad/Display Menu Structure
Main Menu
Enter Password
Quick Menu
View Status
Unit State=_________
Unit Status=________
MWU Status=_______
System Mode= ______
ClgIntrLock= _______
Dehum Status=______
Ctrl Mode= Off
Occ Mode= Auto
Commission Unit
Manual Control
Service Menus
Advanced Menus
Trending Set-Up
Unit Maintenance
BMS Communications
Alarm Lists
About This Unit
IM 1287 • REBEL APPLIED ROOFTOP
Enter Password
About This Unit
Enter Password *******
SO_Item= 123456_12345
Unit SN= FBOU123456789
App Version= 2506018xxx
Cf1-15= xxxxxxxxxxxxxxxx
Cf6-29= xxxxxxxxxxxxxxxx
Main BSP= X.XX
LON BSP= X.XX
LON App Ver= X.XX
BACnet BSP= X.XX
HMI GUID=
xxxxxxxx-xxxx-xxxx-xxxx-
xxxxxxxxxxxx
OBH GUID=
xxxxxxxx-xxxx-xxxx-xxxx-
xxxxxxxxxxxx
OM 1288
Quick Menu
Unit State=_____________
Unit Status=____________
MWU Status=___________
Dehum Status=__________
System Mode= Local
ClgIntrLock=____________
DH Bleeddown=_________
Ctrl Mode= Off
Occ Mode= Auto/Net
Clg Capacity= XXX%
OAD Position= XXX%
Htg Capacity= XXX%
Rht Cap= XXX%
Control Temp= XXX°F
Occ Clg Spt= 72.0°F
Occ Htg Spt= 68.0°F
Disch Air= XXX°F
DAT Clg Spt= 55.0°F
DAT Htg Spt= 85.0°F
54
Unit Operation
for more details.
Min DAT Limit= 55.0°F
Unocc Clg Spt= 85.0°F
Unocc Htg Spt= 55.0°
SAF Capacity= XXX%
SAF Duct Press= X.Xin
SAF DSP Spt= 1.0in
RF/EF Cap = XXX%
Bldg Press= X.XXin
BldgSP Spt= 0.05in
RAF DuctPress=X.XX in
RAF DSP Spt= -1.0 in
CO2 PPM = XXXXppm
OA Flow= XXXXXCFM
MinOAFlw Spt= 2000CFM
SAF Flow= XXXXXCFM
SAF Flow Spt= 2000CFM
OA Temp = XXX°F
Rel Hum1 = XXX%
Rel Hum2 = XXX%
www.DaikinApplied.com