ABB ACS880-604 Hardware Manual page 97

3-phase brake units as modules
Hide thumbs Also See for ACS880-604:
Table of Contents

Advertisement

ACS880-
Frame
Resistor values
604-...
size
R
min
Ohm
U
= 400 V
N
0500-3
R8i
1.7
0750-3
R8i
1.2
1000-3
2×R8i
1.7
1510-3
2×R8i
1.2
2260-3
3×R8i
1.2
3010-3
4×R8i
1.2
3770-3
5×R8i
1.2
U
= 500 V
N
0630-5
R8i
2.2
0940-5
R8i
1.4
1260-5
2×R8i
2.2
1880-5
2×R8i
1.4
2830-5
3×R8i
1.4
3770-5
4×R8i
1.4
4710-5
5×R8i
1.4
U
= 690 V
N
0870-7
R8i
3.0
1300-7
R8i
2.0
1730-7
2×R8i
3.0
2600-7
2×R8i
2.0
3900-7
3×R8i
2.0
5200-7
4×R8i
2.0
6500-7
5×R8i
2.0
No overload use
R
I
I
max
1
2
Ohm
A DC
A DC
2.1
781
282
1.4
1171
424
2.1
1562
565
1.4
2342
847
1.4
3514
1271
1.4
4685
1694
1.4
5856
2118
2.6
781
284
1.7
1171
430
2.6
1562
568
1.7
2342
860
1.7
3514
1289
1.7
4685
1719
1.7
5856
2149
3.6
781
283
2.4
1171
425
3.6
1562
567
2.4
2342
850
2.4
3514
1275
2.4
4685
1700
2.4
5856
2125
Ratings with R
max
Cyclic load (1 min / 5 min)
P
I
I
contmax
max
dc
(S
)
n
kW
A DC
A DC
(kVA)
500
312
827
750
468
1241
1000
625
1655
1510
937
2482
2260
1405
3723
3010
1874
4964
3770
2342
6205
630
312
835
940
468
1277
1260
625
1671
1880
937
2555
2830
1405
3832
3770
1874
5110
4710
2342
6387
870
312
833
1300
468
1249
1730
625
1665
2600
937
2498
3900
1405
3746
5200
1874
4995
6500
2342
6244
Technical data 97
I
P
rms
br
A DC
kW
291
530
436
800
581
1060
872
1600
1308
2400
1744
3190
2180
3990
293
670
449
1030
587
1340
898
2060
1347
3080
1795
4110
2244
5140
293
920
439
1390
585
1850
878
2770
1316
4160
1755
5540
2194
6930

Advertisement