Operating The As-I; Master Start-Up; Configuration Mode - bihl+Wiedemann C Series User Manual

As-i master module
Table of Contents

Advertisement

C-Series AS-i Master Module

Operating the AS-i

7.
Operating the AS-i
The LabVIEW API ships with two examples "AS-i RT Basic.lvproj" and
"AS-i FPGA Basic.lvproj" referenced throughout the rest of this Manual. The ex-
amples can be located by the following steps:
1.
Open LabVIEW if not already opened.
2.
In LabVIEW click Help > Find Examples and then search for "AS-i".
3.
Open the AS-i RT Basic or AS-i FPGA Basic project.
4.
For addition help, click Help > Bihl-Wiedemann in LabVIEW to open the
user manual.
7.1

Master Start-Up

Connect the AS-i module as described in section <Connection samples for
the AS-i power supply> and plug the AS-i module into one slot of your pow-
ered cRIO chassis. All LEDs of the module should be Off.
Then if you run the example "BW-3023 AS-i Commissioning.vi" as described
in section <Configuration Mode> some LED's should turn ON, depending on
the state of master.
1.
If the AS-i network is not sufficiently powered.
AS-i powered
Off
2.
If the AS-i network is sufficiently powered.
AS-i powered
On
On the VI Frontpanel press the the "Operation Mode" switch and notice your
modules being marked in the address table, then press the "Store Actual
Configuration" button, to turn OFF the Config Error LED.
7.2

Configuration Mode

All slaves, except the slave with zero address, that are members of the list of de-
tected slaves (LDS) shall be automatically detected and activated in the above
mentioned way according to AS-i specification.
Configuration mode is demonstrated in both shipping examples referenced in
section <Examples of address assignment>. The AS-i C-Series module can be
placed into configuration mode by completing the following steps:
1.
Connect the AS-i C-Series module as described in section <Connection of
the AS-i Master>.
2.
Open the "AS-i RT Basic.lvproj" example.
Subject to technical modifications; no responsibility is accepted for the accuracy of this information
Internet: www.bihl-wiedemann.de • Flosswoerthstr. 41 • D-68199 Mannheim
AS-i active prj mode
Off
If configuration mode is active,
LED is 'on'. Otherwise 'off'.
AS-i active prj mode
On
If configuration mode is active,
LED is 'on'. Otherwise 'off'.
config error
On
config error
If there is config
error, LED is 'on'.
Otherwise, 'off'.
© Bihl+Wiedemann GmbH
phone: +49 621 33 996-0 • fax: +49 621 3 39 22 399
Tab. 7-8.
Tab. 7-9.
17