Appendix: Codes indicated by the Display

8.
Appendix: Codes indicated by the Display
Bihl+Wiedemann AS-i error codes and warnings are in the range: Range +/-
389000 to 389099. Errors explanations can be found with the NI LabVIEW envi-
ronment by clicking Help "Explain Error". A list of error codes is shown below:
Code
-389000
-389001
-389002
-389003
-389004
-389005
-389006
-389007
-389008
Subject to technical modifications; no responsibility is accepted for the accuracy of this information
Internet: www.bihl-wiedemann.de • Flosswoerthstr. 41 • D-68199 Mannheim
Name
asiErrorAnalogInvali-
dAddress
asiErrorAnalogInvalid-
DataLength
asiErrorAnalogOpera-
tionTimeout
asiErrorCommandInval-
idRequestLength
asiErrorCommand-
Timeout
asiErrorDigitalInvali-
dAddress
asiErrorDigitalInvalid-
Data
asiErrorDigitalInvalid-
DataImageLength
asiErrorSpiFrameData-
Fault
Description
Slave address for the analog read or write is
invalid. Solution: Specify an address in the range
of 0 to 31.
The data length of four 16-bit analog channel is
out of range. Solution: Make sure the data length
is within 8 bytes.
Analog read or analog write timed out. Solution:
Increase timeout and ensure "AS-i Commit.vi"
has been called.
Command request size is out of range. Solution:
Make sure the length of command request is
smaller than 39 bytes.
Timeout occurred waiting for the command
response. Solution: Increase timeout and check
hardware connection.
Slave address for digital read or digital write is
invalid. Solution: Specify an address which is in
the range of 0 to 63.
Digital data value is invalid. Solution: Specify a
value in the range of 0 to 15.
Digital data image size is out of range. Solution:
Make sure the length of digital data image is
smaller than 33 bytes.
CRC check failed between backplane and mod-
ule. SPI communication may be corrupted by
electrical noise. Solution: Reduce noise and con-
tact National Instruments if the error persists.