Technical Specifications; Data Sheet - bihl+Wiedemann C Series User Manual

As-i master module
Table of Contents

Advertisement

C-Series AS-i Master Module

Technical Specifications

4.
Technical Specifications
4.1

Data sheet

Article No. BW3023: AS-i 3.0 Master for Compact RIO and Labview
Function
AS-i I/O data and status information is mapped into the PLC
processor's I/O data.
Article No.
AS-i
Operating current
Operating voltage
AS-i cycle time
Total power dissipation
Display
LED AS-i powered (green)
LED AS-i active (green)
LED prj mode (yellow)
LED config error (red)
Environment
Applied standards
Operating temperature
Storage temperature
Intended environment
Maximum altitude for use
Maximum relative humidity
Pollution degree of the intended
environment
Protection category
acc. EN 60529
Voltage of insulation
Article No.
Weight
Dimensions (W / H / D in mm)
Subject to technical modifications; no responsibility is accepted for the accuracy of this information
Internet: www.bihl-wiedemann.de • Flosswoerthstr. 41 • D-68199 Mannheim
BW3023
approx. 40 mA out of AS-i
approx. 50 mA out of the backplane
AS-i voltage 29,5 ... 31,6 V
DC
150 s * (number of slaves + 2)
max. 1,5 W
on: AS-i voltage O.K.
AS-i normal operation active
configuration mode active
on: at least 1 configured AS-i slave is missing, or at least 1 detected AS-i Slave is not configured, or
for at least 1 configured and detected AS-i slave the actual configuration data does not match the
nominal configuration data, or the master is in the startup process
flashing: peripheral fault
EN 61000-6-2 : 2005
EN 61000-6-4 : 2007 + A1:2011
th
IEC 60079-0, 6
edition
th
IEC 60079-15, 4
edition
EN 60079-0 : 2012 + A11:2013
EN 60079-15: 2010
ISA 12.12.01 : 2013
th
UL 60079-0 : 6
Edition
th
UL 60079-15 : 4
Edition
CSA C22.2, No 223 : 1987 (R2013)
-40 °C ... +70 °C
-40 °C ... +85°C
for indoor use only
5000 m
90%, non condensing
II
housing IP20
(only suitable for use in electrical operating rooms/cabinets with IP54 minimum protection rating)
AS-i to compactRIO:
500 V
60 V
CAT I Ch-to-Earth Isolation
DC
BW3023
420 g
23 / 71 / 89
AS-i Scope
Diagnostics, which go far beyond the standard diagnostics facili-
tate the simple detection of the occasionally occurring configura-
tion
errors
and
further
communication.
So in case of an error the down time of machines can be mini-
mized or you can initiate preventive maintenance.
phone: +49 621 33 996-0 • fax: +49 621 3 39 22 399
irritations
towards
the
AS-i
11
© Bihl+Wiedemann GmbH

Advertisement

Table of Contents
loading

This manual is also suitable for:

Bw 3023