Commercial Air Conditioning SERVICE MANUAL Model HCFU-18CF03 HCFU-18HF03 HCFU-28CF03 HCFU-28HF03 Features Long distribution pipe and high drop Auto-check function Flexible and easy installation Fresh air hole, more natural, more healthy Infrared remote controller & wired controller Optional safety devices and much more precision control device Manual code: SYJS-010-06REV.1...
”D” stands for duct, “P” stands for cabinet type, ”Q” stands for chiller system, "E" stands for ceiling concealed type, “U” stands for outdoor unit Haier 1.2 Brief Introduction for T1 T2 T3 working condition Climate type Type...
Page 4
Commercial Air Conditioner Model: HCFU-18/28CF03 HCFU-18/28HF03 1.4 Product features 1.4.1 Outdoor unit Flexible and easy installation The outdoor can meet the higher request of installation. From the specifications, you will find for each unit, how long and how high the piping will be, which will be convenient for design and installation. Optional safety devices and much more precision control device a.
Commercial Air Conditioner Model: HCFU-18/28CF03 HCFU-18/28HF03 2. SPECIFICATION item Model HCFU-18CF03 Function cooling heating 16500 ----- Capacity BTU/h Capacity 4.83 ----- Sensible heat ratio Total power input 2000 ----- Max. power input 2500 ----- EER or COP ----- Dehumidifying capacity 10 ³×m³/h...
Page 6
Commercial Air Conditioner Model: HCFU-18/28CF03 HCFU-18/28HF03 item Model HCFU-18HF03 Function cooling heating Capacity BTU/h 16500 18000 Capacity 4.83 5.275 Sensible heat ratio Total power input 2000 1800 Max. power input 2500 2400 2.93 EER or COP Dehumidifying capacity 10 ³×m³/h Power cable section 3G×2.5mm...
Page 7
Commercial Air Conditioner Model: HCFU-18/28CF03 HCFU-18/28HF03 item Model HCFU-28CF03 Function cooling heating 24000 ----- Capacity BTU/h ----- Capacity Sensible heat ratio Total power input 2800 ----- Max. power input 3400 ----- 2.54 ----- EER or COP Dehumidifying capacity 10 ³×m³/h Power cable section 3G×4.0mm...
Page 8
Commercial Air Conditioner Model: HCFU-18/28CF03 HCFU-18/28HF03 item Model HCFU-28HF03 heating cooling Function Function Capacity BTU/h 24000 26000 Capacity Sensible heat ratio Total power input 2850 2800 Max. power input 3500 3400 EER or COP 2.54 Dehumidifying capacity 10 ³×m³/h Power cable section 3G×4.0mm Signal cable...
Page 9
Commercial Air Conditioner Model: HCFU-18/28CF03 HCFU-18/28HF03 Installation state: the unit should be placed on the flat floor or be mounted in horizontal direction. Testing method: mounting-on-ceiling unit: outdoor unit: 1.air outlet from side: the noise level is the average sound pressure level measured from front, left, right directions. 2.air outlet from top: the noise level is the average sound pressure level measured from front, back, left, right directions.
Commercial Air Conditioner Model: HCFU-18/28CF03 HCFU-18/28HF03 3. Safety precaution of indoor and outdoor Carefully read the following information in order to operate the airconditioner correctly. Below are listed three kinds of Safety Cautions and Suggestions. WARNING! Incorrect operations may result in severe consequences of death or serious injuries. CAUTION! Incorrect operations may result in injuries or machine damages;...
Page 11
Commercial Air Conditioner Model: HCFU-18/28CF03 HCFU-18/28HF03 WARNING! No goods or nobody is permitted to Installed electrical-leaking circuit placed on or stand on outdoor unit. breaker. It easily cause electrical shock without The falling of goods and people may circuit breaker. cause accidents.
Commercial Air Conditioner Model: HCFU-18/28CF03 HCFU-18/28HF03 5 Installation Instructions 5.1 Installation of indoor unit STANDARD PARTS The following installation parts are furnished. Use them as required. Accessory parts Qty. Remote controller Battery Wire clamp Heat insulation sheathing Screw cap Remote controller bracket Pipe connection requirement...
Page 15
Commercial Air Conditioner Model: HCFU-18/28CF03 HCFU-18/28HF03 (Fig. 4) (Fig. 5) 99cm Wall 24.5cm 50cm Wall bracket 10cm Side of set Indoor unit outdoor unit 6.5cm 7cm hole For series 14,18,24 when installing set to wall, install 3.5cm hole the accessory wall bracket at the position shown in Fig.5,and mount the set to it.
Page 16
Commercial Air Conditioner Model: HCFU-18/28CF03 HCFU-18/28HF03 1. DRILLING FOR PIPING Select piping and drain directions. For series 28,36,42,52.only rear side (Fig.11) (Fig. 11) Rear (Install the drain hose in the direction.) Right CAUTION Install the drain hose at the rear; it should not be installed on the top or right side. 2.
Page 17
Commercial Air Conditioner Model: HCFU-18/28CF03 HCFU-18/28HF03 (Fig. 15) Hex bolt 8 to 13mm Indoor unit (Fig. 16) Apply the indoor unit to the brackets.(Fig.16) Bracket Bolt Indoor unit Now, securely tighten the hex bolts in both sides. 5. INSTALL THE DRAIN HOSE Select whether the drain hose will be connected to the left or right side.(Fig.3) Insert the drain hose into the drain pan, then secure the drain hose with a nylon fastener.(Fig.6) Wrap the insulation (drain hose)around the drain hose connection.(Fig.7)
Page 18
Commercial Air Conditioner Model: HCFU-18/28CF03 HCFU-18/28HF03 HOW TO CONNECT WIRING TO THE TERMINALS A. For solid core wiring (or F-cable)(Fig.19A) (1) Cut the wire with a wire cutter or wire-cutting pliers, then strip the insulation to about 25mm of the exposed solid wire. (2) Using a screwdriver, remove the terminal screw(s) on the terminal board.
Page 19
Commercial Air Conditioner Model: HCFU-18/28CF03 HCFU-18/28HF03 1. INDOOR UNIT SIDE (1) Remove the electric component box. (Fig. 21) (Fig. 22) Electric component box CAUTION Do not remove the screws. If the screws are removed, the electric component box will fall. Remove the four tapping screws.
Page 20
Commercial Air Conditioner Model: HCFU-18/28CF03 HCFU-18/28HF03 (4) Wiring (1) Remove the cord clamp. (2) Process the end of the connection cords to the dimensions. (3) Connect the end of the connection cord fully into theterminal block. (4) Fasten the connection cord with a cord clamp. (5) Fasten the end of the connection cord with the screw.
Page 21
Commercial Air Conditioner Model: HCFU-18/28CF03 HCFU-18/28HF03 MOUNT THE COVER PLATE AND THE INTAKE GRILL Note: The following installing procedure only for series 14,18,24 1.Mount the cover plate. (Right) (1) Cut a pipe exit hole in the right plate. This is only when the pipe exits from the right side. (This operation is not required when the protrusion is on the top or rear.) (Fig.
Page 45
Commercial Air Conditioner Model: HCFU-18/28CF03 HCFU-18/28HF03 [FAN] [HIGH] high fan speed [FAN] [MED] medium fan speed [FAN] [LOW] low fan speed [FAN] [FIX] fixed fan speed, it will display only when fixed fan speed is requested to main indoor unit. [CENTRAL] central control mode [OPERATION]...
Page 46
Commercial Air Conditioner Model: HCFU-18/28CF03 HCFU-18/28HF03 AUTO operation, COOLING, HEATING and DEHUMIDIFICATION operation 1) Start up operation: press the button of ON/OFF, the system will start up, and will display [MODE][AUTO] [FAN][AUTO] [ROOM TEMP.]+ 24 [CLOCK]+”12 00”. 2) Select MODE: press the MODE button, then you will see in the display section [MODE] switch over in below sequence:[FAN ONLY] [COOL] [DRY]...
Page 47
Commercial Air Conditioner Model: HCFU-18/28CF03 HCFU-18/28HF03 TIMER ON, press [TIMER]. [TIMER][ON] will be constant on. Then [TIMER] [OFF] flashes, press the clock +/- button to adjust the time of TIMER OFF, press [SET]. The time sequence of timer on and timer off will determine the mode is [TIMER] [ON] [OFF] or [TIMER] [OFF] [ON].
Page 48
Commercial Air Conditioner Model: HCFU-18/28CF03 HCFU-18/28HF03 CENTRAL control function When the central controller selects [CENTRAL] mode, the buttons in the wired controller except for [CHECK] will be invalid. VENTILATION mode (only for the unit with fresh air function or heat recovery function) Press [RECOVERY] button, then the unit will switch over the ventilation mode: [VENTILATION][AUTO]...
Page 49
Commercial Air Conditioner Model: HCFU-18/28CF03 HCFU-18/28HF03 Preset Outdoor total capacity Actual value, decimal In check mode, press [CHECK] to quit the check mode, and go into normal running mode. How to change the function switches? Type State of Function description switch Changeover Wired...
Page 50
Commercial Air Conditioner Model: HCFU-18/28CF03 HCFU-18/28HF03 There is no lock function only in the wired controller. But when it is connected with a central controller, if the central controller is set to “central”, the buttons in the wired controller will be invalid, or the buttons will be valid.
Page 51
Commercial Air Conditioner Model: HCFU-18/28CF03 HCFU-18/28HF03 Address on Indoor unit SW2-3 SW2-2 SW2-1 SW1-4 SW1-3 SW1-2 SW1-1 central address controller...
Page 52
Commercial Air Conditioner Model: HCFU-18/28CF03 HCFU-18/28HF03...
Page 53
Commercial Air Conditioner Model: HCFU-18/28CF03 HCFU-18/28HF03...
Page 54
Commercial Air Conditioner Model: HCFU-18/28CF03 HCFU-18/28HF03...
Page 55
Commercial Air Conditioner Model: HCFU-18/28CF03 HCFU-18/28HF03 Electrical functions of wired controller: 1.Function difference between master wired controller and slave one: Contrastive items Master wired controller Slave wired controller Function All of functions Only with below functions: ON/OFF, MODE, FAN SPEED, SET TEMP., SWING 2.
Page 56
Commercial Air Conditioner Model: HCFU-18/28CF03 HCFU-18/28HF03 connected with indoor unit is called master one, the other is called slave one. Master wired controller and indoor unit; master and slave wired controllers are all connected through 3 pieces of polar wire. 3.
Commercial Air Conditioner Model: HCFU-18/28CF03 HCFU-18/28HF03 9 ELECTRICAL CONTROL FUNCTIONS 9.1 Control Features The brief introduction includes those for each item of various types of air conditioners and The brief introduction includes those for each item of various types of air conditioners and their electric control functions.
Page 61
Commercial Air Conditioner Model: HCFU-18/28CF03 HCFU-18/28HF03 (2) Auto Selection of Wind Speed In the following, Tr means room temperature while Ts means setting temperature. a. During cooling program conversion of wind speed from the low to high won’t work until the present speed has continued for 3 minutes while conversion from the high to low needs no time delay.
Page 62
Commercial Air Conditioner Model: HCFU-18/28CF03 HCFU-18/28HF03 blowing fan runs at setting wind speed. This working area is defined as area A. (2) Ts Tr Ts + 2 , the compressor and outdoor blowing fan run for 10 minutes then pause for 6 minutes, while indoor blowing fan runs at low wind speed. This working area is defined as area B.
Page 63
Commercial Air Conditioner Model: HCFU-18/28CF03 HCFU-18/28HF03 setting wind speed. (6) Afterheat blowing during heating program During heating program, the compressor will stop running (except overheat protection or frost removal) while the indoor blowing fan will firstly run for 50 seconds at low speed then stop.
Page 64
(12) Monitoring of remote network Through preset interface, the air conditioner is connected to remote control detector (made by Haier) with 2-core cables for wire communication, to execute instructions sent from computer or centralized controller via remote control detector and meanwhile send present running status and trouble information of the machine to remote control detector.
Page 65
Commercial Air Conditioner Model: HCFU-18/28CF03 HCFU-18/28HF03 9.2 Defrost operation flow chart Come to defrost Compressor Open outdoor fun Compressor Condition off or 55s? E-Heat off for 30s? compress Return Operation indoor fun motor Return 4-way value Turn off compressor Return outdoor fun compressor Compressor...
Commercial Air Conditioner Model: HCFU-18/28CF03 HCFU-18/28HF03 10. Diagnostic information (troubleshooting) 10.1 System failure If the refrigerant in the system cannot flow fluently or the airflow circles more slowly, please check due to the following procedures. Cooling: bad cooling if set temp. is proper change the set temp.
Page 67
Commercial Air Conditioner Model: HCFU-18/28CF03 HCFU-18/28HF03 10.2 Failure code The remote receiver, wired controller and indoor PCB indicator all can indicate the failure code. Failure code with wired controller YR-E12: Failure central Failure description Reason remote code control, type, flash wired failure code times...
Page 68
Commercial Air Conditioner Model: HCFU-18/28CF03 HCFU-18/28HF03 10.3 Diagnose and troubleshooting: 1) Sensor failure check if the wiring is correct according to reconnect wiring diagram if sensor is fixed Relocate well Is sensor short-circuit Replace sensor or open-circuit? Is sensor resistance Replace sensor acceptable? Is DC voltage between...
Commercial Air Conditioner Model: HCFU-18/28CF03 HCFU-18/28HF03 11. Electric data 11.1 Wiring diagram HCFU-18CF03 HCFU-18HF03...
Page 71
Commercial Air Conditioner Model: HCFU-18/28CF03 HCFU-18/28HF03 HCFU-28CF03 HCFU-28HF03 0010577269 CIRCUIT DIAGRAM OF INDOOR UNIT W:WHITE B:BLACK R:RED Y:YELLOW TRANS. REMOTE REMOTE OR:ORANGE BL:BLUE CONTROLLER RECEIVER BR:BROWN GR:GRAY CENTRALIZED Y/G:YELLOW/GREEN CAP.:FAN MOTOR CAPACITOR TRANS.:TRANSFORMER CN12 CN16 CN13 OUTDOOR CN11 PRESSURE CN15 SWITCH CONTROL UP-DN FLOAT...
Page 72
Commercial Air Conditioner Model: HCFU-18/28CF03 HCFU-18/28HF03 11.2 Circuit diagram and printed diagram HCFU-18CF03...
Page 73
Commercial Air Conditioner Model: HCFU-18/28CF03 HCFU-18/28HF03...
Page 74
Commercial Air Conditioner Model: HCFU-18/28CF03 HCFU-18/28HF03 Port Function 0010400020 cooling only Chip TMP87PH46N 1CA2 Primary side of transformer Without sequence RTB-1.5-2P Second side of transformer Without sequence B3B-XH Sensor B4B-XH 1 2-TM 3 4-EX Outdoor unit wire B2P3-VH 1 3-N OF Swing motor B5B-XH 1-12VDC 2~5-ABCD Swing motor B5B-XH...
Page 75
Commercial Air Conditioner Model: HCFU-18/28CF03 HCFU-18/28HF03 HCFU-18HF03...
Page 76
Commercial Air Conditioner Model: HCFU-18/28CF03 HCFU-18/28HF03...
Page 77
Commercial Air Conditioner Model: HCFU-18/28CF03 HCFU-18/28HF03 Port Function 0010400019 heat pump Chip TMP87PH46N 1CA2 Primary side of transformer Without sequence RTB-1.5-2P Second side of transformer Without sequence B3B-XH Sensor B4B-XH 1 2-TM 3 4-EX Outdoor unit wire B4P7-VH 1 3 5 7-N OF V QZ Swing motor B5B-XH 1-12VDC 2~5-ABCD Swing motor B5B-XH...
Page 78
Commercial Air Conditioner Model: HCFU-18/28CF03 HCFU-18/28HF03 HCFU-28 0010451167 PCB information circuit diagram...
Page 79
Commercial Air Conditioner Model: HCFU-18/28CF03 HCFU-18/28HF03 0010451167 PCB information characters on board (horizontal)
Page 80
Commercial Air Conditioner Model: HCFU-18/28CF03 HCFU-18/28HF03 0010451167 characters on board vertical...
Page 81
Commercial Air Conditioner Model: HCFU-18/28CF03 HCFU-18/28HF03 Condition for the PCB data: 1.Working ambient temperature: 10 70 , relative humidity:30% 95% 2.Preserved ambient temperature: 20 relative humidity 30% 95% 3.Power supply:220VAC 50/60Hz voltage range:160V 250V 4.Precise of temperature control: 1 0010451167 PCB information – port and definition connect to external power supply, live line: L (220VAC) connect to external power supply, neutral line: N (0VAC) P3 4 5 6...
Page 82
Commercial Air Conditioner Model: HCFU-18/28CF03 HCFU-18/28HF03 lamp 0VDC,6. signal output of power lamp 0VDC, 7. signal output of water pump running lamp 0VDC CN14 control external load, auto elevating function 1. signal of door switch close, 2. output of elevating direction control 0VDC, 3. output of elevating power control 0VDC, 4. power supply 12VDC CN15 input signal, detecting water level of float switch 1-3 short circuit is normal, cut off shows...
Page 83
Commercial Air Conditioner Model: HCFU-18/28CF03 HCFU-18/28HF03 0010451167 PCB information – function selection ON is 1, OFF is 0 The standard condition for PCB in factory SW1 4 bits are OFF SW2 4 bits are OFF SW3 4 bits are ON SW4 2 bits are ON SW5 4 bits are ON SW1-SW2: used for indoor unit to set unit address from 1 to 16’...
Page 84
Commercial Air Conditioner Model: HCFU-18/28CF03 HCFU-18/28HF03 0010451167 PCB information- control type Control type selection between remote and wired: select by dip switch J1, SW3-1 1 means remote control 0means wired control . For remote control type, please use remote controller, and a remote receiver is equipped with indoor unit. Door card control: controls ON/OFF, the start up setting will comply with last time request memorized according to condition memorize function.