Condition for the PCB data:
1.Working ambient temperature: 10
2.Preserved ambient temperature: 20
3.Power supply:220VAC 50/60Hz voltage range:160V 250V
4.Precise of temperature control: 1
0010451167 PCB information – port and definition
P1
connect to external power supply, live line: L (220VAC)
P2
connect to external power supply, neutral line: N (0VAC)
P3 4 5 6
control external load, neutral line: N1 N2 N3 N4(0VAC)
P7
control external load, if there is outdoor PCB, electrical heat: HEAT (control output 220VAC); if
there is not outdoor PCB, compressor control function(control output 220VAC).
P8
control external load, if there is outdoor PCB, health function: OXYGEN (control output
220VAC); if there is not outdoor PCB, 4-way valve control(control output 220VAC).
P9
control external load, if there is outdoor PCB, humidification: HUMI (control output 220VAC); if
there is not outdoor PCB, outdoor fan motor control(control output 220VAC).
P10
control external load, SWING(control output 220VAC)
P11
control external load, WATER PUMP(control output 220VAC)
P12
control external load, indoor fan motor low speed: L(control output 220VAC)
P13
control external load, indoor fan motor mid speed: M(control output 220VAC)
P14
control external load, indoor fan motor high speed: H(control output 220VAC)
P15
communication with fixed frequency single outdoor unit: COMM(0~220VAC)
P16
input control, signal live line: L'(220VAC)
P17
input control, signal neutral line: N'(0VAC)
CN1
input port of transformer (220VAC)
CN2
input port 1 of transformer (no use)
CN3
input port 2 of transformer (no use)
CN4
input port 3 of transformer (1-2 14VAC 3-4 12VAC)
CN5
input control, connecting port to wired controller: CONTROLLER three bits: 1. power supply:
12VAC, 2. power supply: 0VAC, 3. communication: COMM. .
CN6
input control, ambient temp.-coil temp. sensor connecting port: ROOM/PIPE 1-2, ROOM, 3-4,
PIPE.
Indoor ambient temp. sensor: R25=23K +-2.5% B25/50=4200K+-3% range: -40 80
Indoor coil temp. sensor: R25=10K +-3% B25/50=3700K+-3% range: -20 90
CN7
control external load, fresh air control: FRESH 1. blank, 2. power supply 0VDC, 3. control
output: 12VDC.
CN8
input signal: FREEZE
CN9
input control no use
CN10
communication with fixed frequency single outdoor unit: (0~12VDC)
CN11
input signal, outdoor pressure switch control function (for the unit without outdoor PCB)
CN12
input signal, external alarm input: ALARM
conditioner stops work.
CN13
input signal, wiring port of remote receiver board: RECEIVE BOARD 1. power supply 5VDC,
2. power supply 0VDC, 3. remote signal, 4. signal output of running lamp 0VDC, 5. signal output of timer
81
Commercial Air Conditioner
70 , relative humidity:30% 95%
80
relative humidity 30% 95%
Model: HCFU-18/28CF03
HCFU-18/28HF03
1-3 short circuit is normal, if cut off, air