Access To Head Internal Part; Position Of The Electrodes And Central Gas Nozzles - Riello RLS 310/M MX Modulating Operation

Table of Contents

Advertisement

5.7

Access to head internal part

The burner leaves the factory set for opening to the right, there-
fore maintaining the pin 1)(Fig. 14) in its housing.
To open the burner towards the right, proceed as follows:
A remove the screw 6) releasing the tie-rod 7)(Fig. 14);
B remove the screws 2);
C open the burner to a maximum of 100-150 mm by rotating
around the hinge and release the cables of the electrodes 5);
D fully open the burner as in Fig. 14;
E undo the screw 4) with pressure test point;
F disconnect the light oil pipes by unscrewing the two swivel fit-
tings 8);
G release the head by lifting it from its housing 3), then take out
the combustion head.
To open the burner from the opposite side, before
removing the pin 1)(Fig. 14), make sure that the 4
screws 2) are tight. Then shift the pin 1) to the op-
posite side, only then is it possible to remove the
WARNING
screws 2); then proceed as described in point C.
5.8

Position of the electrodes and central gas nozzles

Check that the electrodes are positioned correct-
ly, as in Fig. 15, complying with the dimensions in-
dicated.
WARNING
20096919
20084880
Installation
Electrodes
20
GB
20085329
Fig. 14
Fig. 15