5.13

Gas feeding

Explosion danger due to fuel leaks in the pres-
ence of a flammable source.
Precautions: avoid knocking, attrition, sparks and
heat.
Make sure the fuel interception tap is closed be-
fore performing any operation on the burner.
The fuel supply line must be installed by qualified
personnel, in compliance with current standards
and laws.
WARNING

5.13.1 Gas feeding line

Key (Fig. 23 - Fig. 24 - Fig. 25 - Fig. 26)
1
Gas input pipe
2
Manual valve
3
Vibration damping joint
4
Pressure gauge with push-button cock
5
Filter
6A Includes:
– filter
– working valve
– safety valve
– pressure adjuster
6B Includes
– working valve
– safety valve
– pressure adjuster
6C Includes
– safety valve
– working valve
6D Includes:
– safety valve
– working valve
7
Minimum gas pressure switch
8
Leak detection control, provided as an accessory or integrat-
ed, based on the gas train code (see manual Burner - gas
train combination" supplied as standard). In compliance with
the EN 676 standard, the leak detection control is compulso-
ry for burners with maximum outputs over 1200 kW.
9
Gasket, for "flanged" versions only
10 Pressure adjuster
11 Train-Burner adaptor, supplied separately
P2 Upstream pressure of valves/adjuster
P3 Upstream pressure of the filter
L
Gas train, supplied separately
L1 The responsibility of the installer
Installation
MBC "threaded"
1
2
D11854
MBC "flanged"
4
1
2
3
P 3
L1
DMV "flanged or threaded"
1
2
3
L1
CB "flanged or threaded"
2
3
1
L1
25
GB
7
8
4
P 2
3
6A
P 3
L1
L
7
8
P 2 6B
5
L
8
7
P 2
5
10
L
8
7
P 2
5
10
L
Fig. 23
11
9
D11855
Fig. 24
6C
11
9
D11856
Fig. 25
6D
11
9
D11857
Fig. 26
20084880

Advertisement

Table of Contents
loading

Table of Contents