Communications wiring
The configuration screens contain the 5 adjustable setpoints:
DCV Start Control setpoint
DCV Maximum Control setpoint
Minimum Damper Position
DCV Maximum Vent Damper Position
Min SAT in DCV Override
These can be adjusted to meet various specifications.

Demand Limiting

The Unit Vent accepts 3 levels of demand limit from the network. In response to a demand limit, the unit
decreases its heating setpoint and increases its cooling setpoint to widen the range in order to immediately lower
the electrical demand. You can change the responding temperature adjustment for both heating and cooling and
each demand level. The response to a particular demand level may also be set to 0.
Unit Ventilator
Integration Guide
24
CARRIER CORPORATION ©2019
All rights reserved